Ensure the temperature sampling position as shown above.
If calculated subcooling value is lower than the design
subcooling value (Table 15), please add refrigerant. Repeat steps
2 through 4.
Liquid
Line Temp
6
7
8
(°F)
Liquid Gauge Pressure (PSI)
55
173
176
179
60
188
191
195
65
204
208
211
70
221
225
229
75
239
243
247
80
259
262
266
85
279
283
287
90
300
304
309
95
322
327
331
100
346
351
355
105
370
376
381
110
397
402
407
115
424
430
435
120
453
459
465
125
483
489
469
Table 14
R-410A Refrigerant Chart - Final Subcooling
Heat Pump Model
BRB-36HWD1N1-M18
Table 15
5.
Adjust refrigerant level to attain proper gauge pressure.
Add refrigerant if the subcooling reading from Table 14 is
lower than the designed value (Table 15).
BTC 761701311 C | 04.2020
Final Subcooling(°F)
9
10
11
12
182
185
188
191
198
201
204
208
215
218
221
225
232
236
239
243
251
255
259
262
270
275
279
283
291
295
300
304
313
318
322
327
336
341
346
351
360
365
370
376
386
391
397
402
413
418
424
430
441
447
453
459
471
477
483
489
502
508
515
521
Design Subcooling
12°F ± 4°F
Bosch Inverter Ducted Packaged Heat Pump 3 Ton | 21
Connect gauges to refrigerant bottle and unit as illustrated
(Figure 27 and 28).
Purge all hoses.
Open tank.
Stop adding refrigerant when subcooling matches the
charging chart (Table 14) Final Subcooling value.
Recover refrigerant if the subcooling reading from Table 14 is
higher than the designed value (Table 15).
13
Figure 28
6.
Stabilize the system.
195
211
Wait 5 minutes for the system condition to stabilize between
adjustments.
229
247
When the subcooling matches the chart, the system is properly
266
charged.
287
309
Remove gauges.
331
Replace service port caps to prevent leaks. Tighten finger
355
tight plus an additional 1/6 turn.
381
7.
Record System Information for reference (Table16). Record system
407
pressures and temperatures after charging is complete.
435
465
The subcooling also can be calculated by pressing check button
after getting T3 and T3L temperatures (refer to table 21).
496
528
Description
Outdoor model number
Measured Outdoor Ambient
Measured Indoor Ambient
Check Condenser Outlet Temp.(T3L)
Check Condenser Temp.(T3)
Calculate subcooling value =T3 -T3L
Table 16
Value
°F
°F
°F
°F
°F
Data subject to change