Bosch BRB-36HWD1N1-M18 Installation & Operation Manual page 31

Inverter ducted packaged heat pump
Table of Contents

Advertisement

Installation & Operation Manual
Error Code
Description
E4
Temperature sensor fault (T3, T4, T5,Th, T3L)
H8
Pressure transducer (PT) fault
F1
High pressure switch (HPS) fault
Table 25
E4 (Temperature sensor fault (T3, T4, T5, Th, T3L)
Diagnosis
Check whether sensor
T3/T4/T5/Th/T3L are
seated and normal
(T4 for Heat Pump only)
Yes
Unplug the sensor, check
whether the resistance of
T3/T4/Th/T3L is in the range
of Table 34
Yes
Unplug the sensor, Check
whether the resistance of T5/Tf
is in the range of Table 35
Yes
Check whether the display the
shows the same error code
when re-powered on
Yes
Figure 40
H8 (Pressure transducer (PT) fault)
Diagnosis
Check whether pressure
transducer (PT) wiring are
seated and normal
Yes
Is the pressure transducer
working properly? Compare
the data between pressure
measurement and No 9
(cooling) or No 10 (heating)
check point value (by pressing
check button)
Yes
Check whether there is the
same fault
Yes
Figure 41
BTC 761701311 C | 04.2020
Handling
No
Reseat the sensor
according to wiring diagram
No
Replace the fault T3/T4
Th/T3L sensor
No
Replace the fault T5/Tf sensor
No
Keep running
Handling
No
Wire according to the
diagram correctly
No
Replace the pressure
transducer
No
Keep running
Bosch Inverter Ducted Packaged Heat Pump 3 Ton | 31
F1 (High pressure switch (HPS) fault)
Diagnosis
Check whether high pressure
switch (HPS) wiring is seated
and normal
Yes
Check whether the
resistance of HPS is close to
0KΩ
Yes
Check whether there is the
same fault
Yes
Figure 42
Handling
Reseat wiring according
No
to thewiring diagram
No
Replace high pressure
switch
No
Keep running
Data subject to change