Gardner Denver RHS20 SCFM Manual page 16

High inlet temperature refrigerated dryer
Table of Contents

Advertisement

5.16 AIR DRYER CONTROLLER
The Air Dry Controller device controls the whole operation of the dryer, and allows the calibration of the operating
parameters. The activation of the hot-gas solenoid valve is driven by means of a probe located at the end of the
evaporator, while a cyclic electronic timer drives the condensate drain solenoid valve at regular intervals.
OPERATION - During the dryer operation, the LED
The 10 LED display indicates the current operating DewPoint, shown by means of three colors (blue-green-red) bar over
the display itself.
Blue section - the operative DewPoint of the dryer is too low: freeze risk ;
Green section - operating conditions ensuring an optimal DewPoint ;
Red section - DewPoint of the dryer too high, the treatment of the compressed air may be improper.
The hot-gas solenoid valve is activated when the DewPoint goes below 37ºF (Set-point) -
deactivated when the DewPoint goes at least over 40ºF (Set-point + t) -
The condensate drain solenoid valve is activated for 2 seconds ( T
To perform the manual test for the condensate drain, press the
SET-UP - The Air Dry Controller is adjusted during the final test of the dryer. In case of particular requirements concerning
the operation management, the user can change the setting of the programmed parameters.The parameters which can be
set up are the following :
Set point - activation temperature of the hot-gas solenoid valve (fix hysteresis - t - equal to 34.7°F).
T
- activation time of the condensate drain solenoid valve.
ON
T
- pause time between cycles of the condensate drain solenoid valve.
OFF
To access the set-up, depress the set button
First appears the Set Point parameter to access the other parameters, sequentially press the set button
To change the value of the selected parameter, depress the set button
shown on the LED display. For the value range and the resolution (value of each single LED), see the following table:
The "out of scale" conditions are indicated by the intermittent flashing of the first and the last LED of the display,
respectively showing the exceeding upper and lower range.
To exit the set-up condition in any moment, press the set button
the system exits the set-up condition automatically.
is on.
) -
ON
button.
for at least 2 seconds,
. In case no operations are made during 2 minutes,
16
LED on - and is
LED off.
LED on - each minute ( T
LED flashing confirms the command.
and then the on button;
35-44º F
33º F
).
OFF
.
the current value is
37º F