12.3.9
Evaluation of the Performance
Operate the unit at cooling/heating operation
mode for fifteen minutes or more.
Measure the temperature of the intake and
discharge air.
Ensure the difference between the intake
temperature and the discharge is more than 8°C
during Cooling operation or more than 14°C
during Heating operation.
12.3.10 Installation of Air Purifying Filter
1
Open the front panel.
2
Remove the air filters.
3
Put the air purifying filter into place as shown
in illustration at right.
Air purifying filter 7
Air fi lter