1. Safety Precautions Read the following “SAFETY PRECAUTIONS” carefully before perform any servicing. Electrical work must be installed or serviced by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit for the model installed. The caution items stated here must be followed because these important contents are related to safety.
Page 4
18. For R410A models, when connecting the piping, do not use any existing (R22) pipes and flare nuts. Using such same may cause abnormally high pressure in the refrigeration cycle (piping), and possibly result in explosion and injury. Use only R410A materials.
2. Specifications CU-2E15PBE Item Unit OUTDOOR UNIT Indoor Unit Combination 2.0kW + 2.5kW Power Source 1 Phase, 230V, 50Hz (Power supply from outdoor unit) 4.5 (1.5 ~ 5.2) Capacity BTU/h 15300 (5120 ~ 17700) Running Current 5.75 Electrical Cooling Operation Power Input 1.23 (0.25 ~ 1.52)
Page 6
Item Unit OUTDOOR UNIT Dry Bulb Wet Bulb Maximum °C Cooling Minimum °C Indoor Operation Range Maximum °C — Heating Minimum °C — Maximum °C Cooling Minimum °C — Outdoor Operation Range Maximum °C Heating Minimum °C Note Specifications are subject to change without notice for further improvement.
CU-2E18PBE Item Unit OUTDOOR UNIT Indoor Unit Combination 2.0kW + 3.2kW Power Source 1 Phase, 230V, 50Hz (Power supply from outdoor unit) 5.2 (1.5 ~ 5.4) Capacity BTU/h 17700 (5120 ~ 18400) Running Current 7.10 Electrical Cooling Operation Power Input 1.52 (0.25 ~ 1.58) Data 3.42 (6.00 ~ 3.42)
Page 8
Item Unit OUTDOOR UNIT Dry Bulb Wet Bulb Maximum °C Cooling Minimum °C Indoor Operation Range Maximum °C — Heating Minimum °C — Maximum °C Cooling Minimum °C — Outdoor Operation Range Maximum °C Heating Minimum °C Note Specifications are subject to change without notice for further improvement.
CU-3E18PBE Item Unit OUTDOOR UNIT Indoor Unit Combination 1.6kW + 1.6kW + 2.0kW Power Source 1 Phase, 230V, 50Hz (Power supply from outdoor unit) 5.2 (1.8 ~ 7.3) Capacity BTU/h 17700 (6140 ~ 24900) Running Current Electrical Cooling Operation Power Input 1.20 (0.36 ~ 2.18) Data 4.33 (5.00 ~ 3.35)
Page 10
Item Unit OUTDOOR UNIT Dry Bulb Wet Bulb Maximum °C Cooling Minimum °C Indoor Operation Range Maximum °C — Heating Minimum °C — Maximum °C Cooling Minimum °C — Outdoor Operation Range Maximum °C Heating Minimum °C Note Specifications are subject to change without notice for further improvement.
CU-4E23PBE Item Unit OUTDOOR UNIT Indoor Unit Combination 1.6kW + 1.6kW + 1.6kW + 2.0kW Power Source 1 Phase, 230V, 50Hz (Power supply from outdoor unit) 6.8 (1.9 ~ 8.8) Capacity BTU/h 23200 (6480 ~ 30000) Running Current Electrical Cooling Operation Power Input 1.68 (0.34 ~ 2.47) Data...
Page 12
Item Unit OUTDOOR UNIT Dry Bulb Wet Bulb Maximum °C Cooling Minimum °C Indoor Operation Range Maximum °C — Heating Minimum °C — Maximum °C Cooling Minimum °C — Outdoor Operation Range Maximum °C Heating Minimum °C Note Specifications are subject to change without notice for further improvement.
Page 13
Multi Split Combination Possibility: A single outdoor unit enables air conditioning of up to two separate rooms for CU-2E15PBE, CU-2E18PBE. A single outdoor unit enables air conditioning of up to three separate rooms for CU-3E18PBE. A single outdoor unit enables air conditioning of up to four separate rooms for CU-4E23PBE.
Page 14
Indoor Unit : CS-ME5PKE, CS-E7/9/12PKEW, CS-E9/12GFEW, CS-ME9/12PB4EA, CS-ME9/12PD3EA Outdoor Unit : CU-2E15PBE 2 Room 1 Room Indoor Unit Capacity (kW) Total Indoor Capacity (kW) Indoor Unit Capacity (kW) Total Indoor Capacity (kW) 16 + 16 16 + 20 16 + 25...
Page 15
Indoor Unit : CS-ME5PKE, CS-E7/9/12/15/18PKEW, CS-E9/12/18GFEW, CS-ME9/12/18PB4EA, CS-ME9/12/18PD3EA Outdoor Unit : CU-3E18PBE 3 Room 2 Room 1 Room Indoor Unit Capacity Total Indoor Capacity Indoor Unit Capacity Total Indoor Capacity Indoor Unit Capacity Total Indoor Capacity (kW) (kW) (kW) (kW) (kW) (kW) 16 + 16 + 16...
Page 16
Indoor Unit : CS-ME5PKE, CS-E7/9/12/15/18/21PKEW, CS-E9/12/18GFEW, CS-ME9/12/18/21PB4EA, CS-ME9/12/18PD3EA Outdoor Unit : CU-4E23PBE 4 Room 3 Room 2 Room 1 Room Indoor Unit Total Indoor Indoor Unit Total Indoor Indoor Unit Total Indoor Indoor Unit Total Indoor Capacity (kW) Capacity (kW) Capacity (kW) Capacity (kW) Capacity (kW)
Page 17
4 Room 3 Room 2 Room 1 Room Indoor Unit Total Indoor Indoor Unit Total Indoor Indoor Unit Total Indoor Indoor Unit Total Indoor Capacity (kW) Capacity (kW) Capacity (kW) Capacity (kW) Capacity (kW) Capacity (kW) Capacity (kW) Capacity (kW) 20 + 20 + 25 + 28 25 + 25 + 40 20 + 20 + 25 + 32...
9. Installation Information CU-2E15PBE 9.1.1 Check Points 9.1.2 The Shapes of the 3-Way Valve Caps of the Outdoor Unit Have Been Changed Accompanying the changes in the shapes of the 3-way valve caps, the tightening method has also been changed.
CU-2E18PBE 9.2.1 Check Points 9.2.2 The Shapes of the 3-Way Valve Caps of the Outdoor Unit Have Been Changed Accompanying the changes in the shapes of the 3-way valve caps, the tightening method has also been changed. Firmly tighten the 3-way valve caps by hand, and then tighten them up by another 30 degrees or so (one-twelfth of a full turn) using a spanner or adjustable spanner.
10. Installation Instruction 10.1 CU-2E15PBE CU-2E18PBE 10.1.1 Select The Best Location If an awning is built over the unit to prevent direct sunlight or rain, be careful that heat radiation from the condenser is not obstructed. There should not be any animal or plant which could be affected by hot air discharged.
10.1.4 Connect the Piping Connecting The Piping To Indoor Unit Please make flare after inserting flare nut (locate at Do not over tighten, over tightening may cause gas leakage. joint portion of tube assembly) onto the copper Piping size Torque pipe.
2. Connect the center hose of the charging set to a vacuum pump with check valve, or vacuum pump adaptor. 3. Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa).
10.1.7 Piping Insulation 1. Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram. Please wrap the insulated piping end to prevent water from going inside the piping. 2. If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by using POLY-E FOAM with thickness 6mm or above.
10.2 CU-3E18PBE CU-4E23PBE 10.2.1 Select The Best Location If an awning is built over the unit to prevent direct sunlight or rain, be careful that heat radiation from the condenser is not obstructed. There should not be any animal or plant which could be affected by hot air discharged.
Outdoor Unit Installation Guidelines Where a wall or other obstacle is in the path of outdoor unit’s intake or exhaust airflow, follow the installation guidelines below. For any of the below installation patterns, the wall height on the exhaust side should be 1200mm or less. 10.2.2 Install The Outdoor Unit After selecting the best location, start installation...
Page 45
CUTTING AND FLARING THE PIPING 1. Please cut using pipe cutter and then remove the burrs. 2. Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused. Turn the piping end down to avoid the metal powder entering the pipe. 3.
Page 46
10.2.5 Connect The Cable To The Outdoor Unit 1. Remove the control board cover metal from 4. Connect the power supply cord and the unit by loosening two screws. connecting cable between indoor unit and 2. Cable connection to the power supply through outdoor unit according to the diagram as isolating Devices (Disconnecting means).
10.2.6 Heat Insulation Use a material with good heat-resistant properties as the heat insulation for the Material shall Liquid-side pipes pipes. Be sure to insulate both the gas-side and liquid-side pipes. If the pipes are withstand Gas-side pipes not adequately insulated, condensation or water leakages may occur. 120°C or higher...
11. Operation Control 11.1 Cooling Operation 11.1.1 Outdoor fan control When cooling operation is enabled, based on outdoor ambient temperature, fan motor control will be adjusted according to figure below: 11.1.2 Annual Cooling control This control is to enable cooling operation when outdoor ambient temperature is low. Control start conditions: Cooling operation is activated with compressor ON.
11.2 Heating Operation 11.2.1 Outdoor fan control When heating operation is enabled, based on outdoor ambient temperature, fan motor control will be adjusted according to figure below for Heating overload control: 11.2.2 Heating Room Temp Sampling Control To improve the judgment accuracy, indoor room temperature sampling starts when any indoor unit has stopped capability supplied (heating thermo-off) during heating operation with compressor ON, outdoor unit will send signal to all thermo-off indoor units to ON fan motor and get room temperature sample.
Page 50
Control Contents Compressor frequency and outdoor fan speed maximum limit is set. Adjust accordingly. Compressor frequency Outdoor fan speed Cool/Quiet #30 Hz #400 rpm Cancel Condition Indoor fan speed is equal or higher than Lo fan. > 1 operation indoor unit. In any cooling overload zone.
12. Simultaneous Operation Control Operation modes which can be selected using the remote control unit: Automatic, Cooling, Dry, Heating and e-ion operation mode. Types of operation modes which can be performed simultaneously Cooling operation and Cooling, Dry or e-ion operation. Heating operation and Heating operation.
13. Protection Control 13.1 Freeze Prevention control (Cool) When received freeze prevention signal from indoor unit, the compressor frequency changes according to indoor heat exchanger temperature. When indoor unit request capability OFF due to freeze condition, immediately the capability supply to targeted indoor unit stops.
13.5 Cooling overload control (Cool) This control detect outdoor pipe temperature and perform the compressor frequency restriction during cooling operation. 13.6 Heating overload control (Heat) This control detect indoor pipe temperature and perform the compressor frequency restriction during heating operation. This control detect outdoor ambient temperature and perform the fan speed adjustment during heating operation.
If the running current does not exceed X value for 5 seconds, compressor frequency will increase. However, if total outdoor unit running current exceeds Y value, compressor will be stopped immediately for 3 minutes. CU-4E23PBE CU-3E18PBE CU-2E18PBE CU-2E15PBE Operation Mode X (A) Y (A) X (A) Y (A)
13.13 Compressor Protection Control (Gas leak detection control 1) Control start conditions For 5 minutes, the compressor continuously operates and total current is low. During Cooling or Soft Dry operation: Indoor intake temperature — indoor piping temperature is below 4°C. During Heating operation: Indoor pipe temperature —...
14. Servicing Mode 14.1 CU-3E18PBE & CU-4E23PBE 14.1.1 Pump down operation (SW1) Operate the pump down process according to the following procedure Confirm the valve on the liquid side and gas side are open. Press PUMP DOWN button (SW1) on the Service PCB inside the outdoor unit for more than 5 seconds. Pump down (cooling) operation is performed for 15 minutes.
14.1.3 Wiring Error Check The unit capable to correct the wiring error automatically by following procedures. Confirm the valve on the liquid side and gas side is open. Press WIRING CHECK button (SW3) on the Service PCB inside the outdoor unit for more than 10 seconds to start wiring check operation.
14.2 CU-2E15PBE & CU-2E18PBE 14.2.1 Pump down operation Operate the pump down process according to the following procedure Confirm the valve on the liquid side and gas side are open. Short the CN-PUMP button on the Service PCB inside the outdoor unit for more than 5 seconds. Pump down (cooling) operation is performed for 15 minutes.
15.2 Self Diagnosis Function (CU-3E18PBE and CU-4E23PBE) The display screen of wireless remote control unit and the self-diagnosis LEDs (green) on the outdoor printed circuit board in the outdoor unit can be used to identify the location of the problem. Refer to the table below to identify and solve the cause of the problem, and then re-start the air conditioner system.
High voltages are generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding with repair work. Failure to heed this caution may result in electric shocks. 16.1 Outdoor Unit Removal Procedure (CU-2E15PBE CU-2E18PBE) Caution! When handling electronic controller, be careful of electrostatic discharge.
16.1.4 Removing the Propeller Fan and Fan Motor 1. Remove the cabinet top plate and cabinet front plate. 2. Remove the propeller fan by removing the nut turning clockwise at its center. 3. Disconnect the connector of the fan motor from the control board.
Page 66
16.2.2 Remove the Control Board Cover and Particular Plates 3. Remove the control board cover (remove 3 screws). 4. Remove the particular plate (remove 2 screws). 5. Remove the particular plate (remove 2 screws). 16.2.3 Removing the Control P.C. Board 6.
Page 67
16.2.4 Removing the Propeller Fan and Fan Motor 1. Follow the steps in 18.2.1 for removing the cabinet top plate and cabinet front plate. 2. Remove the propeller fan by removing the nut turning clockwise at its center. 3. Disconnect the fan motor connector from the control P.C.
18. Exploded View and Replacement Parts List 18.1 CU-2E15PBE CU-2E18PBE Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 101
SAFETY REF. NO. DESCRIPTION & NAME Q’TY CU-2E15PBE CU-2E18PBE REMARK CHASSIS ASSY CWD52K1277 ← FAN MOTOR BRACKET CWD541167 ← FAN MOTOR, AC 50W SINGLE ARW6405AC ← SCREW-FAN MOTOR BRACKET CWH551217 ← SCREW-FAN MOTOR MOUNT CWH55252J ← PROPELLER FAN CWH03K1066 ←...
18.2 CU-3E18PBE CU-4E23PBE Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 104
SAFETY REF. NO. DESCRIPTION & NAME QTY. CU-3E18PBE CU-4E23PBE REMARK CHASSIS ASSY CWD52K1212 ← SOUND PROOF BOARD CWH151194 ← FAN MOTOR BRACKET CWD541127 ← SCREW-BRACKET FAN MOTOR CWH551217 ← CONDENSER COMPLETE CWB32C2680 ← FAN MOTOR DC 60W 3PH EHDS80C60AC ← SCREW-FAN MOTOR MOUNT CWH551323 ←...