Hacousto Holland bv
Industrieweg 87
2651BC Berkel & Rodenrijs
4E-FMWB installation and user guide

4. Hardware installation and settings

Housing installation

4E-FMWB is dedicated to wall mounting by means of four wall plugs or screws, directly to the wall structure.
Before fixing the housing:
1. Make sure that there is enough room to open the front door after the housing is fixed;
2. Make an opening for the network cable in any wall of the 4E-FMWB (except the front door) and
secure it with a cable gland.
Mount the housing at an average line of sight, with its center approximately 160cm above floor.

L-Net

4E-FMWB is a remote station connected to an L-Net port of 4EVAC main unit. Multiple 4E-FMWB stations
may be used in the same L-Net, with the following limitations:
A maximum of 8 stations per L-Net port
A maximum of 16 stations per single 4EVAC main unit (total sum of all 3 L-net ports)
The microphone station may be also daisy-chained together with other L-Net devices
Page 6 of 17