Integrated Fireman Mic - 4EVAC 4E-FMWB Installation And User Manual

Table of Contents

Advertisement

Hacousto Holland bv
Industrieweg 87
2651BC Berkel & Rodenrijs
4E-FMWB installation and user guide
5.2.5.2.
Use this combination to trigger the silence instruction to the previously selected zones. If no zones are
selected, this starts silence on all zones accessible from local front panel.
NOTE: If any EVAC input is active during manual zone silence, the activation trigger will override SILENCE
mode.
5.2.5.3.
Use this combination to reset the Compact 500 system. In a network system this will reboot the entire
network. If reset was triggered successfully, all local LED indicators should start their fast blinking sequence
during reboot.

6. Integrated fireman mic

The front panel of the 4E-FMWB is equipped with a Fireman Microphone. Take out the handheld
microphone and press the PTT button to enable LIVE EVAC signal transmission to all zones available on
the local panel. This signal is a top priority audio stream and will override any other type of audio signal in
the system.
If any zone was previously selected, you will start transmitting only to the selected zones.
Page 15 of 17
FUNCTION + SILENCE
FUNCTION + RESET
Author:
Triggering manual EVAC
DD

Advertisement

Table of Contents
loading

Table of Contents