4E-CMT installation and user guide
SUMMARY
This document includes both installation and user guides of 4E-CMT, the commercial purpose microphone
station with touchscreen for the 4EVAC Voice Evacuation System. It explains how the 4E-CMT should be
installed and configured. The installation instructions are addressed to trained technical personnel, such as
installers, service technicians and commissioning engineers. The user instructions explain how to operate
the 4E-CMT and how to interpret indications by the end users as well as technical personnel, such as service
technicians.
Rev.
Date
REVISION AND APPROVAL
01
04-09-2019
02
05-06-2020
Page 1 of 13
Nature of Changes
Original draft
Corrections
Author:
Approved By
DD
TvdH
DD

Advertisement

Table of Contents
loading

Summary of Contents for 4EVAC 4E-CMT

  • Page 1 The installation instructions are addressed to trained technical personnel, such as installers, service technicians and commissioning engineers. The user instructions explain how to operate the 4E-CMT and how to interpret indications by the end users as well as technical personnel, such as service technicians.
  • Page 2: Table Of Contents

    2651BC Berkel & Rodenrijs Author: 4E-CMT installation and user guide Table of Contents 1. What is the 4E-CMT? ................................3 2. Where do I start? ..................................3 3. Configuration settings ................................4 4. Hardware installation and settings ............................ 5 L-Net ....................................5 4.1.1.
  • Page 3: What Is The 4E-Cmt

    4E-CMT is connected to the L-Net interface of the 4EVAC system main unit and may be daisy-chained with more L-Net devices. 4E-CMT is dedicated for call points where only general purpose paging is required. 4E-CMT is compatible with all 4EVAC voice evacuation panels, including Compact 500 and Impact.
  • Page 4: Configuration Settings

    3. Configuration settings Settings for the 4E-CMT are included in the configuration file located on the micro SD memory card installed in the 4EVAC system main unit. This configuration file includes user-defined settings, such as: zone selection buttons;...
  • Page 5: Hardware Installation And Settings

    4. Hardware installation and settings L-Net 4E-CMT is a remote station connected to the L-Net port of the C500 main unit. Multiple microphone stations may be used in the same L-Net, with the following limitations: A maximum of 8 stations per L-Net port...
  • Page 6: Redundant Link

    Industrieweg 87 2651BC Berkel & Rodenrijs Author: 4E-CMT installation and user guide 4.1.2. Redundant link If you need to make a redundant L-Net connection to the Compact 500 main unit, connect both L-Net ports of the device to two L-Net ports on the C500 main unit. You can choose any L-Net port on the C500 main unit.
  • Page 7: Network Cabling

    4E-CMT installation and user guide 4.1.3. Network cabling 4EVAC network features a full duplex RS-422 data link and 24V DC power to remote devices. If you’re building a distributed system using the 4EVAC network, you should make physical links between devices using the right cables.
  • Page 8: Device Id

    Make sure the ID value exists in your configuration settings, relates to the right device type and is not duplicated to another device. Allowed values: 01-FE 4. Set the Device ID value according to the configuration settings of the 4EVAC system. Plug-in the L-Net cable connecting the station with the 4EVAC main unit.
  • Page 9: Front Panel

    4E-CMT installation and user guide 5. Front Panel NOTE: 4E-CMT does not support emergency mode. Evacuation features are not available for this device. As long as the system is activated in voice alarm condition (EVAC mode), all general paging features are also not accessible.
  • Page 10: Start Paging

    Hacousto Holland bv Industrieweg 87 2651BC Berkel & Rodenrijs Author: 4E-CMT installation and user guide 5.1.3. Start paging TALK STOP SILENCE button button button Use the TALK button to start paging in selected zones. If no zones are selected, pressing the TALK button will start paging in all zones available on this panel (ALL CALL).
  • Page 11: More Tab

    Under the “MORE” tab you will find buttons used for starting and stopping user programmable events, for example: starting transmission of pre-defined BGM input to a pre-defined group of zones. For more information about programming events, please look in the user manual of the 4EVAC Manager, where all configuration settings are explained.
  • Page 12: Technical Specifications

    Hacousto Holland bv Industrieweg 87 2651BC Berkel & Rodenrijs Author: 4E-CMT installation and user guide 6. Technical specifications 4E-CMT Number of zones max. 255 zones (global network access) Controls and indications RGB touchscreen witch user-configurable buttons: zone / group selection,...