Status Leds - HID Mercury LP4502 Installations And Specifications

Table of Contents

Advertisement

Powering
Trusted Identities

2.10 Status LEDs

2.10.1 Power-up
All LEDs are OFF.
2.10.2 Initialization
After power is applied or reset switch pushed, LED 1 is ON for about 15 seconds, then LEDs 2, 3, 4, 5, 6, R1, R2,
IN1, IN2, IN3, IN4, IN5, IN6, IN7 and IN8 are flashed once at the beginning of initialization. LEDs 3 and 4 is
turned ON for approximately 1 second after the hardware initialization has completed, then the application
code is initialized. The amount of time the application takes to initialize depends on the size of the database,
about 1 second without a card database. Each 10,000 cards will add about 2 seconds to the application
initialization. When LEDs 1, 2, 3 and 4 flash at the same time, data is being read from or written to flash
memory, do not cycle power when in this state. If the sequence stops or repeats, perform the bulk erase
procedure, see
Bulk erase configuration
2.10.3 Running
After initialization is complete, the LEDs have the following meanings:
LED
Description
1
Off-line / On-line and battery status
Off-line = 20% ON, On-line = 80% ON
Double flash if battery is low
2
Host communication activity (Ethernet)
3
Internal SIO communication activity
4
External SIO communication activity (Port 1)
5
External SIO communication activity (Port 2)
R1
Reader 1: Clock/Data or D1/D0 Mode = Flashes when data is received, either input.
F/2F mode: Flashes when data/acknowledgment is received
RS-485 mode = Flashes when transmitting data
R2
Reader 2: Clock/Data or D1/D0 Mode = Flashes when data is received, either input.
F/2F mode: Flashes when data/acknowledgment is received
RS-485 mode = Flashes when transmitting data
YEL
Ethernet speed: OFF = 10Mb/S, ON = 100Mb/S
GRN
OFF = No link, ON = Good link, Flashing = Ethernet activity
D16
Ethernet activity
IN1
Input IN1 status: OFF = Inactive, ON = Active, Flash = Fault
IN2
Input IN2 status: OFF = Inactive, ON = Active, Flash = Fault
IN3
Input IN3 status: OFF = Inactive, ON = Active, Flash = Fault
IN4
Input IN4 status: OFF = Inactive, ON = Active, Flash = Fault
IN5
Input IN5 status: OFF = Inactive, ON = Active, Flash = Fault
IN6
Input IN6 status: OFF = Inactive, ON = Active, Flash = Fault
IN7
Input IN7 status: OFF = Inactive, ON = Active, Flash = Fault
PLT-05246, A.4
memory.
1
17
HID Mercury™ LP4502 Controller
Installation and Specifications
1
1
1
1
1
1
June 2021

Hide quick links:

Advertisement

Table of Contents
loading