4.5
Electric connection
The power supply of the cPIA
located above the panoply at the top.
4.5.1

Electrical protection

EC
Grounding the cPIA
is imperative.
EC
For the cPIA
without electrical resistance it is necessary to install a 2A circuit breaker. The minimum cable cross
section is 1.5 mm².
In the event that there's an electrical resistance, a 16A circuit breaker must be installed. The minimum section of
the cable is 2.5 mm². The line feeding the cPIA
4.5.2

EC centrifugal fan

- Ball bearings
- 230V~ 50/60Hz
- Class F winding
- IP44 protection
- Temperature range from -20°C to +50°C
- 146mm diameters turbine, double inlet
4.5.3

Safety thermostat

Reset
Off-set T° range
Security
Central fixing
Contact
Off-set power
Capilary break lenght
Capilary termination
Capilary isolated lenght
The responsibility of EUREVIA cannot be engaged if problems due to an incorrect or non-existent grounding
appears.

5. Starting

5.1

Functional test

- Make sure that the unit is correctly installed and placed (§2) and that the drainage pipe is not clogged
EC
is made by a single point through the quick connector
EC
must have a differential device of 30mA.
Automatic
80-86°C
Positive
By nut
Unipolar
16(3)A
500 mm
Wounded
350 mm
EUREVIA - ZI Athélia 5 – 369 avenue des Grenadiers - 13600 La Ciotat -
FRANCE Phone : +33 (0)4 42 70 70 30
www.eurevia.com
Tension
Manual
89-95°C
Positive
By nut
Unipolar
16(3)A
500 mm
Wounded
350 mm