VLC-800MX 17A-03-VLC 12/08 Fig. 1 Xtralis Vesda VLC-800MX TECHNICAL SPECIFICATION WARNING: Type Identification Value: The Xtralis VESDA VLC incorporates a System Compatibility: Use only with MX Fire Laser device and is classified as a Class 1 Alarm Controllers Laser product which complies with FDA...
The MX version of the VESDA VLC acts as a smoke sensor Alarm with external LED: 3.3mA on the Tyco MX loop and reports directly to the MX Fire relay: rated 2A @ 30V dc controller.
VLC-800MX 17A-03-VLC 12/08 Red FIRE LED: Indicates that a fire condition SCOPE OF THIS DOCUMENT has been detected. Also, when This manual provides instructions on how to install, configured to flash-when-polled commission and operate the VESDA VLC-800MX. It outlines it will normally flash once the standard pipe configurations permissible, power supply every 5 seconds with a double requirements, and some installation tips.
Page 6
VLC-800MX 17A-03-VLC 12/08 MAXIMUM PIPE LENGTH 80m 4mm END HOLE 3-15 OFF 2.5mm SAMPLING HOLES MAXIMUM PIPE LENGTH 50m 2 OFF 4MM END HOLES 2-9 OFF 3mm SAMPLING HOLES (PER PIPE) Fig. 6 Pre-engineered Pipework Configurations PRE-ENGINEERED SOLUTIONS FOR Where the VESDA detector is located remote from the protected area (for example in a corridor outside the room) SECONDARY SAMPLING then consideration must be given to returning the detector...
VLC-800MX 17A-03-VLC 12/08 MOUNTING BRACKET 8mm FIXING HOLES 112. 5 112. 5 E = CABLE ENTRY POINT ON REAR OF ENCLOSURE Fig. 8 VLC-800 Mounting Bracket MOUNTING THE DETECTOR When positioning the detector ensure that sufficient space is allowed for pipe and cable conduit connections. Xtralis BRACKET suggests that there is at least 150mm of clear space around the air inlet pipe and cable entry points to allow for pipe and...
All conductors must be free of earths. Monitor input (PSM) terminals on the VLC-800MX in order to inform the Tyco Panel of any faults. This input is c) Remove the required push out plugs for monitored and requires a 47k End-of-Line resistor. The cable entry.
VLC-800MX 17A-03-VLC 12/08 VLC800 TERMINATION CARD FROM CONTROLLER OR PREVIOUS DEVICE RS232 PORT FOR TO NEXT DEVICE VCONFIG PRO OR CONTROLLER CONNECTION REMOTE LED PROGRAMMING EXTERNAL RELAY PORT REL- DRIVE REL+ EXTERNAL SUPPLY PSM- FAULT RELAY PSM+ ONBOARD EXTERNAL RELAY RELAY EXTERNAL 24V SUPPLY...
VLC-800MX 17A-03-VLC 12/08 3) Customised thresholds can be set using a 9.11 USING AutoLearn PC running VLC. Customised thresholds may be appropriate in particular circumstances but should be used with caution. For example, the default alarm threshold of 0.2% may be inappropriate for a system protecting a small area (using fewer holes than the maximum allowed) with a background level around 0.15% obscuration/m.
VLC-800MX 17A-03-VLC 12/08 Action Frequency Details Check Power supplies Every month Test according to suppliers instructions. Note: Where the condition of the battery is regularly checked automatically, less frequent manual checks may be applicable. Check the pipework Every 6 months Check that all pipe runs are intact, that pipe supports and joints are firm and that the sampling holes are free of dirt.
VLC-800MX 17A-03-VLC 12/08 Fig. 16 Removal/Replacement of Aspirator Assembly 11. TROUBLE SHOOTING 11.1 INTERROGATING FAULT CONDITIONS The VLC-800MX fault status is communicated via the MX loop and more implicitly on the LEDs on the front of the unit. See below for a description of LED behaviour: Service LED: If this LED is lit fault(s) on the detector are serviceable by a field technician without the need to replace components.
Page 18
VLC-800MX 17A-03-VLC 12/08 12. ORDERING INFORMATION VLC-800MX VESDA Laser COMPACT: 516.018.012 Air Filter Cartridge: 516.018.504 Xtralis: VSP-005 Aspirator Fan: 516.018.515 Xtralis: VSP-015 VESDA 24V dc 2A Power Supply: 516.018.407 Xtralis: VSP-220 13. APPROVALS The VLC-800MX is CE marked to the Construction Products Directive (CPD) supported by an EC Certificate of Conformity (0832-CPD-0770 issued by BRE Global) to EN 54-20.