Product BFL (M) Belimo BFN (M) -R (FDC 25) Klimaoprema -R (FDC 40) -EMP (FDC 25/40) SOLID AIR ® CLIMATE SOLUTIONS • T +31 598 36 12 21 • www.solid-air.nl • mail@solid-air.nl 4 | Circular fire damper user manual 05/2020...
Page 5
* (dimension X is same as Y 125 - 180 Øn + 95 mm (blade lenght outside of housing) 200 - 315 Øn + 80 mm but opposite side SOLID AIR ® CLIMATE SOLUTIONS • T +31 598 36 12 21 • www.solid-air.nl • mail@solid-air.nl...
Page 7
Fill the space between the damper according to table screws (screw hole is 6 mm in and the slab with mortar (on page 6) diameter) SOLID AIR ® CLIMATE SOLUTIONS • T +31 598 36 12 21 • www.solid-air.nl •...
Page 8
Fill the space between the damper Cover the mortar with GKF gypsum and the wall with mortar boards (12.5 mm thick) SOLID AIR ® CLIMATE SOLUTIONS • T +31 598 36 12 21 • www.solid-air.nl •...
Page 9
Fill the space between the damper and Cover the mortar with GKF gypsum the wall with mortar boards (12.5 mm thick) SOLID AIR ® CLIMATE SOLUTIONS • T +31 598 36 12 21 • www.solid-air.nl •...
Page 10
Cover the mineral wool with GKF gypsum boards (12.5 mm thick) SOLID AIR ® CLIMATE SOLUTIONS • T +31 598 36 12 21 • www.solid-air.nl •...
Page 11
*The Kit is universal for all dimensions and must be cut to fit the specific dimensions of the damper Cover the mortar with GKF gypsum boards (12.5 mm thick) SOLID AIR ® CLIMATE SOLUTIONS • T +31 598 36 12 21 • www.solid-air.nl •...
Page 12
Connections of mineral wool seal with intumescent fire resistant sealant (e.g. Promastop-I or Hilti CFS-CT). Mineral wool and damper casing must be coated with 2 mm thick fire protection coating SOLID AIR ® CLIMATE SOLUTIONS • T +31 598 36 12 21 • www.solid-air.nl •...
Page 13
Place the wool on insulation on damper ends (80 mm x ventilation duct in lenght of 80 mm 80 mm, 1 mm thick metal sheet cover) SOLID AIR ® CLIMATE SOLUTIONS • T +31 598 36 12 21 •...
Page 14
Washer, galvanized steel Nut, galvanized steel Bracket, 45x30x1,5 mm, galvanized steel L shaped profile (50x50x1) secured with self tapping screw to damper housing SOLID AIR ® CLIMATE SOLUTIONS • T +31 598 36 12 21 • www.solid-air.nl • mail@solid-air.nl 14 | Circular fire damper user manual 05/2020...
Page 15
Space between casing and wall minimal distance of 30 mm between close with mortar wall, ceiling or other dampers. Cover the mortar with GKF gypsum boards (12.5 mm thick) SOLID AIR ® CLIMATE SOLUTIONS • T +31 598 36 12 21 • www.solid-air.nl •...
Page 16
30 mm between close with mortar wall, ceiling or other dampers. Mineral wool and damper casing must be coated with 2 mm thick fire protection coating SOLID AIR ® CLIMATE SOLUTIONS • T +31 598 36 12 21 • www.solid-air.nl •...
Page 17
Space between casing and wall Fire damper can be installed with minimal distance of 30 mm between close with mortar wall, ceiling or other dampers. SOLID AIR ® CLIMATE SOLUTIONS • T +31 598 36 12 21 • www.solid-air.nl •...
Page 18
(density 140 kg/m³) Mineral wool and damper casing must be coated with 2 mm thick fire protection coating SOLID AIR ® CLIMATE SOLUTIONS • T +31 598 36 12 21 • www.solid-air.nl •...
Page 19
Fire damper can be installed with Space between casing and wall minimal distance of 30 mm between close with mortar wall, ceiling or other dampers. SOLID AIR ® CLIMATE SOLUTIONS • T +31 598 36 12 21 • www.solid-air.nl •...
Page 20
Øn + 115 mm 125 - 180 Øn + 95 mm Øn + 105 mm 200 - 315 Øn + 80 mm Øn + 90 mm SOLID AIR ® CLIMATE SOLUTIONS • T +31 598 36 12 21 • www.solid-air.nl • mail@solid-air.nl...
Manual activation: Push the release button. • Self-operating activation: With a fuse at 72 ºC Resetting: • Manual reset: Turn the screwdriver counter clockwise SOLID AIR ® CLIMATE SOLUTIONS • T +31 598 36 12 21 • www.solid-air.nl • mail@solid-air.nl...
Page 22
For this version with remote activation, the double contact S (OPEN/CLOSED) are mounted as standard equipment • The 4-contact - S2 - are available as an option (factory option or after-sales kit) SOLID AIR ® CLIMATE SOLUTIONS • T +31 598 36 12 21 •...
Spring: 1 second Spring: 1 second Blade opening time Manual Degree of protection IP 42 IP 42 SOLID AIR ® CLIMATE SOLUTIONS • T +31 598 36 12 21 • www.solid-air.nl • mail@solid-air.nl 23 | Circular fire damper user manual 05/2020...
(temperature in the duct) max. 72 °C temperature sensor on the inner side of the duct (temperature in the duct) max. 72 °C SOLID AIR ® CLIMATE SOLUTIONS • T +31 598 36 12 21 •...
Page 25
II of the directive 94/9/EC. SOLID AIR ® CLIMATE SOLUTIONS • T +31 598 36 12 21 •...
After each intervention, provide a systematic cleaning of dust and especially the solenoid and its movable plate • Check the if the electrical terminals are tightened SOLID AIR ® CLIMATE SOLUTIONS • T +31 598 36 12 21 • www.solid-air.nl •...
Page 27
Harmonised standard EN 15650:2010 SOLID AIR ® CLIMATE SOLUTIONS • T +31 598 36 12 21 • www.solid-air.nl • mail@solid-air.nl 27 | Circular fire damper user manual 05/2020...
Page 28
Solid Air Postbus 14, 9610 AA Sappemeer, Netherlands +31 20 696 69 95 mail@solid-air.com www.solid-air.com...
Need help?
Do you have a question about the FDC25 Series and is the answer not in the manual?
Questions and answers