Section 3
Secure system setup
GUID-9C3524CC-091F-4333-A707-FAC0A835C1ED V5 EN-US
Figure 2:
Distribution substation example
3.2
10

Relay communication interfaces

Some physical ports dedicated for station bus communication can be opened and
closed in relay configuration. Few ports are always open as they are needed in
communication for monitoring, control and configuration. The front port is used
for engineering and it can be used only for point-to-point configuration access with
PCM600.
Table 1:
Physical ports on relay's communication cards
Port ID
Type
A2
RJ-45
A2
RS-485
Front port
USB
Serial ports are closed by default and Ethernet ports are open. All protocol
instances, except for IEC 61850 and FTP, are by default off and do not respond to
protocol requests in serial or Ethernet ports. The IEC 61850 protocol and rear
Default state
Description
Open
Ethernet station bus
Closed
Serial station bus
Closed
Service access
Cyber Security Deployment Guideline
2NGA000818 A