Password Policies - ABB RELION REX610 Manual

Protection and control cyber security deployment guideline
Hide thumbs Also See for RELION REX610:
Table of Contents

Advertisement

2NGA000818 A
4.2
REX610
Cyber Security Deployment Guideline
the relay over FTP/FTPS. Authentication on the LHMI is required to use USB
communication with PCM600.
If the PCM600 authentication has been enabled in PCM600 System
Settings, a relay user can be linked to the current PCM600 user by
selecting the Remember me check box in the Login dialog. After
that, the user credentials are no longer asked at tool communication
as logging in PCM600 also provides the authentication credentials
to the protection relay.
The Administrator user shall not be allowed to delete the last
ADMINISTRATOR user and itself. FTP/FTPS logins are done by
entering the username and password; there is no role selection
required. The highest role for the username is automatically
selected by the protection relay. Performing the Restore Factory
settings operation in IED Users in PCM600 restores user accounts
to the factory user accounts.

Password policies

Passwords are settable for the user accounts in all roles. Only the following
characters are accepted.
Numbers 0-9
Letters a-z, A-Z
Space
Special characters !"#%&()*+'-./:;<=>?@[]^_`{|}~
There are default password policies in the protection relay.
Minimum password length: 4
Maximum password length: 8
Minimum uppercase characters: 0
Minimum numeric: 0
Minimum special characters: 0
The protection relays are delivered from the factory with default passwords. It is
required to change the default passwords.
Section 4
User management
17

Advertisement

Table of Contents
loading

Table of Contents