Hoshizaki KML-200MAE Service Manual page 16

Modular crescent cuber
Hide thumbs Also See for KML-200MAE:
Table of Contents

Advertisement

1) Defrost Control
A thermistor (Semiconductor) is used for a defrost control sensor. The resistance varies
depending on the Suction Line temperatures. The Thermistor detects the temperature
of the Evaporator outlet to start the Defrost Timer. No adjustment is required. If neces-
sary, check for resistance between Thermistor leads, and visually check the Thermistor
mounting, located on the Suction Line next to the Evaporator outlet.
Check a thermistor for resistance by using the following procedures.
(i) Disconnect the connector K3 on the board.
(ii) Remove the Thermistor. See "V. 11. REMOVAL AND REPLACEMENT OF THER-
MISTOR."
(iii) Immerse the Thermistor sensor portion in a glass containing ice and water for 2 or 3
minutes.
(iv) Check for a resistance between Thermistor leads.
Normal reading is within 3.5 to 7kW. Replace the Thermistor if it exceeds the normal
reading.
2) Defrost Timer
No adjustment is required under normal use, as the Defrost Timer is adjusted to the
suitable position. However, if necessary when all the ice formed on the Evaporator
does not fall into the bin in the harvest cycle, adjust the Defrost Timer to longer position
by setting the Dip Switch (No. 1 & 2) on the Controller Board.
Dip Switch
No. 1
OFF
ON
OFF
ON
Temperature (°F)
0
10
32
50
70
90
SETTING
Dip Switch
No. 2
OFF
OFF
ON
ON
Resistance ( W)
14.401
10.613
6.000
3.871
2.474
1.633
60 seconds
90 seconds
120 seconds
180 seconds
16
TIME