result in short circuit, fire, malfunctions. FG Terminal must be used a dedicated ground. Not doing so
could result in malfunctions.
a. Grounding should be the Class 3 grounding. The cable for grounding should be more than 4㎟.
b. grounding point be closed to the products and make short the distance to the ground cable if possible.
Please see below.
■ Installation Precautions
Do not install the location which exceeds allowed temperature. Product can be damaged or shorten
the life. Especially Install environment as below should be avoided.
Do not Install product to the place which the ambient temperature is out of limits, from 0℃ to 50℃ or on the
surface of control board which high pressure equipment is installed.
Do not install to the place where strong shock or vibration continuously have impacted on product.
The space between back of product and back of control board must be more than 100mm for maintenance
and ventilation.
In order to improve water retention and ventilation, the space between the back of the main body
and the console box should be 100mm or more, and install the cooling fan when installed in an
enclosed space.

■ Disposal Precautions

When you dispose of product and battery, please treat it as industrial waste. It can create poisonous
substances or explosion.

■ Cell Type Battery Specifications and Exchange

Mounted on mainboard Model MS920SE Battery is not replaced by the user. If the battery has run out of
service, please contact our Customer Support Center for replacement and inspection.
Item
Content
Battery Voltage
DC 3V
Battery Model
MS920SE (lithium / Rechargeable )
Battery lifetime
Permanent (In case of ambient temperature 25℃)
Battery Discharge Last about 7 days After turn it off
* Depending on the model specifications are subject to change.
■ All field-wiring connections to this unit shall be from Limited Voltage / Limited Current, below 24 Vdc
isolated secondary source with an output fuse, or Class 2.
M2I Corporation
11-35, Simin-daero 327beon-gil, Dongan-gu, Anyang-si, Gyeonggi-do 14055, Korea, Tel: +82-70-465-3366, Fax: +82-31-465-3355, www.m2i.co.kr