WAGO Gateway Installation and Service

Connecting the Plug-in Attachment

Legend
A Plug-in attachment with terminator (standard delivery)
Legend
A Plug-in attachment (standard delivery)
B Terminator
WAGO BACnet/IP gateway
The plug-in attachment (standard delivery) must be
plugged in.
Do not connect the plug-in attachment until the CAN
bus cable has been connected.
If the gateway is at the beginning or end of the CAN bus:
If the gateway is not at the beginning or end of the
CAN bus:
Plug in the plug-in attachment without the terminator.
Use the plug-in attachment for looping through the
CAN bus.