3. Setup

1) Secure the legs to the condenser unit with eight M8 × 16mm hexagon bolts and M8
nuts as shown in the illustration. See Fig. 6.
Note: Locate the legs symmetrically.
2) The legs have eight mounting holes. Secure the legs with eight bolts (not included).
3) Install enough length of two copper tubings provided with Parker quick connect
couplings between the icemaker and the condenser unit. The two copper tubings
should be insulated separately. See Fig. 7.
Note:
Precharged tubing kits, available as optional equipment from HOSHIZAKI
AMERICA, are recommended.
4) Line sets fabricated in the field should be evacuated through the charging ports on
the Parker quick connect couplings and charged with R-404A refrigerant vapor to a
pressure of 15 - 30 PSIG.
Note: Factory fabricated tubing kits are precharged and do not need to be
evacuated.
5) Remove the plastic caps protecting the couplings. Attach the two refrigerant lines to
the male couplings on the icemaker and the remote condenser unit. Each refrigerant
line must be connected as follows:
• Icemaker discharge refrigerant line - 1/2" OD tubing to "DIS" of condenser unit
• Icemaker liquid refrigerant line - 3/8" OD tubing to "LIQ" of condenser unit
Note: Make the connections at the remote condenser first and then at the icemaker.
Fig. 6
15
Fig. 7