Inspection; Limitations; General - Pioneer YD024GMFI18MR2 Installation Instructions Manual

Split system heat pump & air conditioner
Table of Contents

Advertisement

4

1.1 INSPECTION

As soon as a unit is received, it should be inspected for possible damage during transit.
If damage is evident, the extent of the damage should be noted on the carrier's delivery
receipt. A separate request for inspection by the carrier's agent should be made in
writing. See Local distributor for more information.
Requirements For Installing/Servicing R410A Equipment
Gauge sets, hoses, refrigerant containers, and recovery system must be designed
to handle the POE or PVE type oils.
Manifold sets should be 800 PSIG high side and 250 PSIG low side with 550 PSIG
Iow side restart.
All hoses must have a 700 PSIG service pressure rating.
Leak detectors should be designed to detect R410A.
Recovery equipment (including refrigerant recovery containers) must be specifi-
cally designed to handle R410A.
Do not use an R-22 TXV.
Good Refrigeration practices require the installation of a field supplied liquid line
drier, as shown in Fig.1.
NOTE
It will be more convenient to open
the Service valve after removing
the Underside Clapboard.
LARGE SERVICE VALVE
SMALL SERVICE VALVE
LIQUID-LINE FILTER-DRIER
FIELD SUPPLIED AND INSTALLED

1.2 LIMITATIONS

The unit should be installed in accordance with all National, State, and Local Safety
Codes and the limitations listed below:
1.Limitations for the indoor unit, coil and appropriate accessories must also be observed.
2.The outdoor unit must not be installed with any duct work in the air stream. The outdoor fan is
the propeller type and is not designed to operate against any additional external static pressure.
3.The maximum and minimum conditions for operation must be observed to assure a system
that will give maximum performance with minimum service.
4.This unit is not designed to operate with a low ambient kit. Do not modify the control system to
operate with any kind of Iow ambient kit.
5.The maximum allowable line length for this product is 100 feet.

2.0 GENERAL

The outdoor units are designed to be connected to a matching indoor coil with braze
connect lines. Units are factory charged with refrigerant for a matching indoor coil
plus 15 feet of field supplied lines.
Matching indoor coils are available with a thermostatic expansion valve or an orifice
for the most common usage. The orifice size and/or refrigerant charge may need to
be changed for some indoor-outdoor unit combinations, elevation differences or
total line lengths.
Fig.1 Filter-Drier installation