F F u u r r n n a a c c e e G G e e n n e e r r a a l l I I n n s s t t a a l l l l a a t t i i o o n n

Twinning

TWINNING CONNECTION DIAGRAM
FOR TWINNING S-SERIES FURNACES
2 STAGE HEAT / 1 STAGE COOLING THERMOSTAT
2 STAGE HEATING
1 STAGE COOLING
THERMOSTAT
FURNACE NO. 1
Y1
W1
W1
W2
W2
R
G
B
TWINNING CONNECTION DIAGRAM
FOR TWINNING S-SERIES FURNACES
2 STAGE HEAT / 2 STAGE COOLING THERMOSTAT
2 STAGE HEATING
1 STAGE COOLING
THERMOSTAT
FURNACE NO. 1
Y1
Y1
Y2
Y2
W1
W1
W2
W2
R
G
B
42
FURNACE NO. 2
Y1
Y1
W1
R1
W2
R2
R
R
G
G
B
B
FURNACE NO. 2
Y1
Y2
ISOLATION RELAY
(FIELD SUPPLIED)
W1
R1
W2
R2
R
R
G
G
B
B
NOTES:
1. BOTH FURNACES MUST BE POWERED FROM
THE SAME 115 VAC PHASE LEG AT THE CIRCUIT BREAKER.
2. TRANSFORMERS MUST BE IN PHASE.
- MEASURE THE VOLTAGE BETWEEN THE "R" TERMINALS
ON BOTH FURNACES, VOLTAGE SHOULD BE LESS THAN
10 VOLTS.
- IF GREATER, REVERSE THE LOW VOLTAGE ON ONE OF THE
TRANSFORMERS AND RECHECK.
3. HEATING AND COOLING AIRFLOW MUST BE THE SAME FOR
BOTH FURNACES.
4. OD UNIT TYPE SETUP MUST BE THE SAME FOR BOTH FURNACES.
5. WHEN TWINNING THE S8B1 / S8X1 FURNACES, DISREGARD THE
W2 AND R2 WIRING.
ISOLATION RELAY
1 STAGE ODU
(NO TRANSFORMER)
R1
Y1
R2
B
NOTES:
1. BOTH FURNACES MUST BE POWERED FROM
THE SAME 115 VAC PHASE LEG AT THE CIRCUIT BREAKER.
2. TRANSFORMERS MUST BE IN PHASE.
- MEASURE THE VOLTAGE BETWEEN THE "R" TERMINALS
ON BOTH FURNACES, VOLTAGE SHOULD BE LESS THAN
10 VOLTS.
- IF GREATER, REVERSE THE LOW VOLTAGE ON ONE OF THE
TRANSFORMERS AND RECHECK.
3. HEATING AND COOLING AIRFLOW MUST BE THE SAME FOR
BOTH FURNACES.
4. OD UNIT TYPE SETUP MUST BE THE SAME FOR BOTH FURNACES.
2 STAGE ODU
ISOLATION RELAY
(NO TRANSFORMER)
R1
Y2
Y1
R2
B
S8XB-SVX001-1A-EN