There are some Dip switched located in the external unit. These may require altering to enable and disable
certain funtions on unit.
Modifications to the Dip switch setting should only be completed with the power off to the unit.
The DIP switches are located on the Terminal PCB.
Frost Protection can be disabled via setting DIP SW1 to the OFF
position DOWN*
*A suitable Anti-Freeze Solution must be used
W:
www.seconrenewables.com

Dip Switch Setting

The Output of the unit Circulation pump can be set Via DIP SW5-6
The Should be set to provide the correct flow rate through the unit:
HPID6R32 –
11.34lpm*
HPID10R32-
19.26lpm*
HPID13R32 –
40.62lpm*
HPID17R32 –
27.90lpm*
T: 0191 516 6554
*Failure to achieve these figures may result in poor
performance or reduced output