The Mono block requires one Supply please find the details below:
*In the case of long cable runs, selection of correct cable must be done in
accordance with BS 7671 (IET Wiring Regulations)
In addition to the heat pump supply above 3 other additional supplies are required: One supply for the EP001
and another for the Immersion heater.
The EP001 requires a 5 amp supply.
The Immersion heater requires a 13amp supply.
The additional pump requires a 3 amp supply
All supplies should be via a double switched isolator and the cables should be sized in accordance with BS7671.
W:
www.seconrenewables.com
Power Supply
Power supply cable (mm²)
Model
Maximum
HPID6R32
4.0
HPID10R32
4.0
HPID13R32
6.0
HPID17R32
6.0
T: 0191 516 6554
Breaker
capacity
Minimum
2.5
16A Class C
2.5
20A Class C
4.0
32A Class C
4.0
32A Class C