Diagnostic Codes/Status of Equipment
E312
Restricted air flow in cooling or continu-
ous fan mode is lower than cfm setting.
E313
Indoor or outdoor unit capacity mismatch.
Communication only.
E331
Global network connection - Communica-
tion link problem.
E334
Relay "Y1" stuck on integrated control.
E347
No 24 Volt output on Y1 of "integrated
control" with non communicating outdoor
unit.
E348
No 24 Volt output on Y2 of "integrated
control" with non?communicating outdoor
unit.
E349
No 24 Volts between R & O on "integrated
control" with non communicating outdoor
unit (Dual fuel module required for heat
pump application
E370
Interlock switch sensed open for 2 min-
utes.
E400
LSOM - Compressor internal overload
tripped.
E401
LSOM Compressor long run cycle or low
system pressure.
E402
LSOM - Outdoor unit system pressure
trip.
E403
LSOM - Compressor short-cycling. .(Run-
ning less than 4 minutes). Outdoor unit
pressure trip
E404
LSOM - Compressor rotor locked. Com-
pressor short-cycling. (Running less than
4 minutes).
E405
LSOM - Compressor open circuit.
TABLE 5 Continued
Ignition Control 103130-XX Diagnostic Codes
Warning Only. Restricted airflow - Indoor blower is running at a re-
duced CFM (Cutback Mode - The variable speed motor has pre-set
speed and torque limiters to protect the motor from damage caused
by operating outside of design parameters (0 to 0.8" W.C.. total ex-
ternal static pressure). Check filter and duct system. To clear, re-
place filter if needed or repair/add duct. Cleared after the current
service demand is satisfied.
Incorrect indoor/outdoor capacity code selected. Check for proper
configuring in installation instructions. Alarm is just a warning. The
system will operate, but might not meet efficiency and capacity pa-
rameters. Alarm will clear when commissioning is exited. Cleared
after commissioning is complete.
For Future Use.
Replace integrated control.
Operation stopped. Y1 relay / Stage 1 failed. (Pilot relay contacts
did not close or the relay coil did not energize; no input back to IFC
chip). Critical Alert. Cleared after reset and Y1 input sensed.
Y2 relay / Stage 2 failed. (Pilot relay contacts did not close or the
relay coil did not energize; no input back to IFC chip). Critical Alert.
Cleared after reset and Y1 input sensed.
Configuration link R to O needs to be restored. Replace link or hard-
wire. Applicable in non communicating mode. Critical Alert.
Control sees the loss of 24VAC for 2 minutes. Terminate all services
and wait for interlock switch to close. The alarm will clear when
24VAC is continuously sensed on DS terminal for a minimum of 10
seconds or on a power reset.
Thermostat demand Y1 is present; but, compressor is not running.
Check power to outdoor unit. Clears the error after current is sensed
in both RUN and START sensors for at least 2 seconds, or after
service is removed, or after power reset.
Compressor ran more than 18 hours to satisfy a single thermostat
demand. Critical Alert. Clears the error after 30 consecutive normal
run cycles or power reset. Also monitors low pressure switch trips.
Discharge or suction pressure out-of-limits, or compressor over-
loaded. Clears the error after 4 consecutive normal compressor run
cycles.
Compressor runs less than 3 minutes to satisfy a thermostat de-
mand. Clears the error after 4 consecutive normal run cycles or
power reset.
Compressor rotor locked up due to run capacitor short, bearings
are seized, excessive liquid refrigerant, etc. Clears the error after 4
consecutive normal run cycles or after power reset.
Compressor circuit open (due to power disconnection, open fuse,
etc.) Clears the error after 1 normal compressor run cycle.
Page 37
Action Required to Clear and Recover