Installation conditions for a fresh duct

Installation information on a fresh duct
f A fresh duct can be installed wiith an indoor unit or with another fresh duct .
f
f A fresh duct should be installed within 50%~100% of outdoor unit's cooling capacity .
f
f If a fresh duct is installed with an indoor unit, the fresh duct should be installed within 30% of outdoor unit's cooling
f
capacity .
f A fresh duct can be installed with HEAT PUMP outdoor unit but cannot be installed with HEAT RECOVERY outdoor unit .
f
- e . g . A fresh duct 28kW + Duct 7 . 1 kW x 9 = 91 . 9 kW
Outdoor unit 33 . 6 + 61 . 6 kW = 95 . 2 kW
Indoor unit combination rate = 96 . 5 %  O . K
Fresh duct combination rate = 29 . 4 %  O . K
Mixture Install
Outdoor : 95.2kW
Fresh
Duct
28kW
- Fresh duct 14kW + Duct 5 . 6 kW x 6 = 47 . 6 kW
Outdoor unit 50 . 4 kW = 50 . 4 kW
Indoor unit combination rate = 95 . 2 %  O . K
Fresh duct combination rate = 28 . 0 %  O . K
Mixture Install
Outdoor : 50.4kW
Fresh
Standard Standard Standard Standard Standard Standard
Duct
14kW
5.6kW
- Fresh duct 14 kW + Fresh duct 22 . 4 kW = 36 . 4 kW
Outdoor unit 40kW = 40kW
Fresh duct combination rate = 91%  O . K
Indoor unit combination rate = 0%  O . K
Only Fresh Air Intake Unit install
Outdoor : 40kW
Fresh
Duct
14kW
22.4kW
Standard Standard Standard Standard Standard Standard Standard Standard Standard
7.1kW
7.1kW
7.1kW
5.6kW
5.6kW
Fresh
Duct
7.1kW
7.1kW
5.6kW
5.6kW
5.6kW
ENGLISH-7
7.1kW
7.1kW
7.1kW
7.1kW