INPUT WIRING

The 2408 CD/CR must be provided with an 80 amp,
120/240 or 120/208Y VAC, three wire electrical service.
This service must include two live wires not exceeding 150
volts to ground and one neutral wire. In addition the unit must
be grounded by conduit or an additional ground wire in accordance
with electrical codes.
The input wiring should be #4 AWG THWN or equivalent copper
wire rated for least 75 C.
Pass the input wiring through the 1 1/4" conduit hole in the top
of the unit. Allow the wires to drop 4-6" into the unit then loop
the wires back upwards. Connect each of the two live wires to the
copper lugs located above the circuit breakers and connect the
neutral wire to the neutral bar. If provided, connect the additional
ground wire to the terminal marked "GND".
120/240 or 120/200 80A
LOADS MAY EXIT TOP
20 AMP
CIRCUIT BRKRS
GND
NEUTRAL BUS
20 AMP CIRCUIT BREAKERS
Figure 2
INPUT WIRING
Installation & Operation Guide
Page 5
20 AMP
CIRCUIT BRKRS
20 AMP CIRCUIT BREAKERS
LIMITED 2 YEAR WARRANTY AND
EXCLUSIONS
Leviton warrants to the original consumer purchaser and not for the benefit
of anyone else that this product at the time of its sale by Leviton is free
of defects in materials and workmanship under normal and proper use for
two years from the purchase date. Leviton's only obligation is to correct
such defects by repair or replacement, at its option. For details visit
www.leviton.com or call 1-800-824-3005. This warranty excludes
and there is disclaimed liability for labor for removal of this product or
reinstallation. This warranty is void if this product is installed improperly or in
an improper environment, overloaded, misused, opened, abused, or altered
in any manner, or is not used under normal operating conditions or not in
accordance with any labels or instructions. There are no other or implied
warranties of any kind, including merchantability and fitness for
a particular purpose, but if any implied warranty is required by the
applicable jurisdiction, the duration of any such implied warranty, including
merchantability and fitness for a particular purpose, is limited to two years.
Leviton is not liable for incidental, indirect, special, or consequential
damages, including without limitation, damage to, or loss of use of,
any equipment, lost sales or profits or delay or failure to perform
this warranty obligation. The remedies provided herein are the exclusive
remedies under this warranty, whether based on contract, tort or otherwise.
TRADEMARK DISCLAIMER
Use herein of third party trademarks, service marks, trade names, brand
names and/or product names are for informational purposes only, are/may
be the trademarks of their respective owners; such use is not meant to imply
affiliation, sponsorship, or endorsement.
FOR CANADA ONLY
For warranty information and/or product returns, residents of Canada should
contact Leviton in writing at Leviton Manufacturing of Canada Ltd to
the attention of the Quality Assurance Department, 165 Hymus
Blvd, Pointe-Claire (Quebec), Canada H9R 1E9 or by telephone at
1 800 405-5320.