CONNECTIONS – PLUMBING
Subject to local regulatory authority approval, the drain lines from the
temperature pressure relief valve and expansion control valve from an individual
water heater may be interconnected.
The outlet of a drain line must be in such a position that flow out of the pipe can
be easily seen, but arranged so discharge will not cause injury, damage or
nuisance. The termination point of a drain line must comply with the requirements
of AS/NZS 3500.4. Drain lines must not discharge into a safe tray.
In locations where water pipes are prone to freezing, drain lines must be
insulated, must not exceed 300 mm in length and are to discharge into a tundish
through an air gap of between 75 mm and 150 mm.
If a drain line discharges into a tundish, the drain line from the tundish must be
not less than DN20. The drain line from a tundish must meet the same
requirements as for a drain line from a relief valve.
Warning: As the function of the temperature pressure relief valve on this
water heater is to discharge high temperature water under certain conditions, it
is strongly recommended the pipe work downstream of the relief valve be
capable of carrying water exceeding 93°C. Failure to observe this precaution
may result in damage to pipe work and property.