1.0 Installation and Startup Guide
Install Environment
Where
The MT-600 Series is designed for industrial. The temperature range of operating is
Used
from 32 to 113 °F (0 to 45 °C) , as majority of industrial environments. It may not be
suitable for using in certain outdoor applications. Please consult the factory for
advised usage in outdoor applications.
NEMA
The MT-600 Series front bezel is NEMA 4 rated. When installed properly in a NEMA
Rating
4 panel, the NEMA 4 rating of the panel will not be compromised. This means that
fluids will not enter the panel during wash downs.
Electrical
The MT-600 Series has been tested to conform to European CE requirements. This
Environment
means that the circuitry is designed to resist the effects of electrical noise. This does
not guarantee noise immunity in severe cases. Proper wire routing and grounding
will insure proper operation.
Mechanical
Avoid installing units in environments where severe mechanical vibration or shocks
Environment
are present.
2.0 Installation Instructions
2.1 Mounting Instructions
2.1.1 Location Considerations
Care should be taken when locating equipment behind the unit to ensure that AC power wiring, PLC
output modules, contactors, starters and relays, and any other source of electrical interference are located
away from the back of the unit.
Particular note should be taken to the position of variable speed drives and switching power supplies.
Their input and load cables should be screened to a central star earth point.
MT-600 series
1
MT-615X
Installation Instruction

Advertisement

Table of Contents
loading

Summary of Contents for weintek MT-615X

  • Page 1 MT-600 series MT-615X Installation Instruction 1.0 Installation and Startup Guide Install Environment Where The MT-600 Series is designed for industrial. The temperature range of operating is Used from 32 to 113 °F (0 to 45 °C) , as majority of industrial environments. It may not be suitable for using in certain outdoor applications.
  • Page 2: Power Connections

    2.1.2 Making a NEMA-4 Mounting Panel The unit can be mounted into panels with a depth of 4”(105mm). It is recommended that Details the unit be mounted on the front panel of a steel enclosure, through an appropriate opening*. Allow a clearance of 1”(25mm) around the sides of the unit for mounting hardware.
  • Page 3 Caution Do not power the MT-600 and inductive DC loads, or input circuitry to the Supply Voltage controller, with the same power supply. Note: The 24 VDC output from Condition some controllers may not have enough current to power the MT-600. Caution Wire lengths should be minimized (Maximum 1600’...
  • Page 4: Communications Connections

    apply to installation of solid-state programmable control devices. In addition, these precautions conform to the guidelines for installation of Controllers as recommended in the NEMA ICS 3-304 Control Standards. Programming To conform with ICS Safety Recommendations, checks should be placed Considerations in the controller to ensure that all writable registers that control critical parts of plant or machinery have limit checks built into the program, with...
  • Page 5 2.3.2 Connector COM1[RS485] , COM3[RS485] and COM3[RS232] The 9 Pin, Female, SUB-D, COM1 [RS-485], COM3 [RS-485] and COM3 [RS-232] Port on the back of the unit is the RS-232 and RS485/422 communications port for connecting to a controller. Connection Pin Designations Pin assignment of the 9 Pin, Female, SUB-D COM1 [RS-485], COM3 [RS-485] and COM3 [RS-232] Port Pin# Symbol Com1...
  • Page 6 2.3.5 Dip Switch SW1 SW2 SW3 SW4 Mode OFF OFF OFF Touch Screen Calibrate mode OFF ON OFF OFF Reserve OFF OFF ON OFF Boot Loader mode OFF OFF OFF ON Reserve OFF OFF OFF OFF Normal Touch Screen Calibrate mode: In this mode when you power on the MT600, the screen will display a “+”...
  • Page 7: Specifications

    3.0 Specifications MT615X Hardware Specification Display 15.0" TFT Brightness 350 cd/m Color 262,144 colors Contrast Ratio 400:1 Resolution (WxH dots) 1024 x 768 Back light CCFLx2 CCFL life time 50,000 hr. min. Touch panel 4 wires resistive type Touch Accuracy Surface Hardness COM1 (RS-232/RS-485 2W/4W), COM2(RS232), COM3(RS-232/RS-485 2W) I/O port...
  • Page 8: Front View

    4.0 Dimensions of MT-615 Top View 366mm [14.41"] Front View Side View 350mm [13.78"] 269mm [10.59"] Power D-sub VGA out Cutout dimensions: MT-615: 352mm [13.86"] W x 279mm [10.98"] H FUSE 1A Reset FUSE5X20 75mm [2.95"] Rear View G H I J Panel-mounting clamp slots, 10 places Bottom View IDE interface (DOM slot)