Advertisement

Quick Links

1.0 Installation and Startup Guide
Install Environment
Where
The MT-600 Series is designed for industrial. The temperature range of operating is
Used
from 32 to 113 °F (0 to 45 °C) , as majority of industrial environments. It may not be
suitable for using in certain outdoor applications. Please consult the factory for
advised usage in outdoor applications.
NEMA
The MT-600 Series front bezel is NEMA 4 rated. When installed properly in a NEMA
Rating
4 panel, the NEMA 4 rating of the panel will not be compromised. This means that
fluids will not enter the panel during wash downs.
Electrical
The MT-600 Series has been tested to conform to European CE requirements. This
Environment
means that the circuitry is designed to resist the effects of electrical noise. This does
not guarantee noise immunity in severe cases. Proper wire routing and grounding
will insure proper operation.
Mechanical
Avoid installing units in environments where severe mechanical vibration or shocks
Environment
are present.
2.0 Installation Instructions
2.1 Mounting Instructions
2.1.1 Location Considerations
Care should be taken when locating equipment behind the unit to ensure that AC power wiring, PLC
output modules, contactors, starters and relays, and any other source of electrical interference are located
away from the back of the unit.
Particular note should be taken to the position of variable speed drives and switching power supplies.
Their input and load cables should be screened to a central star earth point.
MT-600 series
1
MT-608S
Installation Instruction

Advertisement

Table of Contents
loading

Summary of Contents for weintek EasyView MT-600 Series

  • Page 1 MT-600 series MT-608S Installation Instruction 1.0 Installation and Startup Guide Install Environment Where The MT-600 Series is designed for industrial. The temperature range of operating is Used from 32 to 113 °F (0 to 45 °C) , as majority of industrial environments. It may not be suitable for using in certain outdoor applications.
  • Page 2: Environmental Considerations

    2.1.2 Making a NEMA-4 Mounting Panel The unit can be mounted into panels with a depth of 4”(105mm). It is recommended that Details the unit be mounted on the front panel of a steel enclosure, through an appropriate opening*. Allow a clearance of 1”(25mm) around the sides of the unit for mounting hardware.
  • Page 3: Grounding Requirements

    Caution Do not power the MT-600 and inductive DC loads, or input circuitry to the Supply Voltage controller, with the same power supply. Note: The 24 VDC output from Condition some controllers may not have enough current to power the MT-600. Caution Wire lengths should be minimized (Maximum 1600’...
  • Page 4: Communications Connections

    Considerations in the controller to ensure that all writable registers that control critical parts of plant or machinery have limit checks built into the program, with an out-of-limit safe shut down procedure to ensure safety of personnel. ICS 3-304.81 Safety Recommendations: Consideration should be given to the use of an emergency stop function, which is independent of the programmable controller.
  • Page 5 2.3.2 Connector COM2 [RS232] Pin Designations Pin assignment of the 9 Pin, Male, SUB-D COM2 [RS-232] Port Pin# Symbol Function Received Data COM2 [RS-232] Transmitted Data Signal Ground Ready to send output Clear to send input Pin 1,6,8 short. 2.3.3 Connector COM3[RS485] Pin Designations Pin assignment of the 9 Pin, Female, SUB-D COM3 [RS-485] Port Pin#...
  • Page 6 2.3.6 Dip Switch SW1 SW2 Mode OFF Touch Screen Calibrate mode OFF ON Boot Loader mode Touch Screen Calibrate mode: In this mode when you power on the MT600, the screen will display a “+” sign at the center of the screen. Use a stylus or finger to push the center of the “+” until it moves. The “+”...
  • Page 7: Specifications

    3.0 Specifications MT608S Hardware Specification Display 7.7" DSTN Brightness 150 cd/m2 Color 4096 colors Contrast Ratio 30:1 Resolution (WxH dots) 640 x 480 Back light CCFLx2 CCFL life time 25,000 hr. min. Touch panel 4 wires resistive type Touch Accuracy Surface Hardness COM1 [RS-232], COM2 [RS232], COM3 [RS485] I/O port...
  • Page 8 4.0 Dimensions of MT-608S Front View Side View Bottom View Cutout dimensions: MT-608S: 222mm(8.74”) W x 167mm(6.57”) H Rear View a. CompactFlash slot g. USB client b. Sound ports h. USB Master c. MIC ports i. Com1[RS232] d. Ethernet port (RJ-45) j.