Reprogramming Factory Installed Tracer Adaptiview Controls (Ctv Firmware) - Trane CVHE Installation Instructions Manual

E-frame retrofit adaptive frequency drive
Table of Contents

Advertisement

Installation
Table 24. UC800/Tracer AdaptiView CVR parameter values with a retrofit AFDH
Tracer TU Service Setpoints View:
Adjustable Frequency Drive Setpoints
AF Control
ReOptimization Sensitivity
Tracer TU Field Startup View:
Adjustable Frequency Drive
Maximum Frequency
Minimum Frequency
AFD Surge Capacity Increase
Tracer TU Configuration View:
Main
Unit Type (MODL)
Starter Type
Tracer TU Configuration View:
UC800
Impeller Diameter (CPIM)
Number of Stages
Tracer TU Configuration View:
Starter
Stop Delay Time (Contactor Interrupt
Failure)
Unit Voltage
Voltage Transformer Ratio
Rated Load Amps (RLA)
CT Meter Scale
Current Unbalance Trip Point
Current Unbalance Grace Period
Maximum Acceleration Setting
Acceleration Time Out Action
Overload Type
Phase Reversal
Contactor Integrity Test
Phase Reversal Grace Period
Surge Protection
Momentary Power Loss
Restart Inhibit Stop to Start Time
Surge Sensitivity
Power Loss Reset Time
Reprogramming Factory Installed Tracer
AdaptiView Controls (CTV Firmware)
Important:
Make sure your laptop is loaded with the
most current version of Tracer TU tool
software so that you have the most up-to-
date version of CTV MP firmware available
to install into the UC800.
Note: CTV MP firmware is always used in factory installed
Tracer AdaptiView control systems or in Tracer
AdaptiView display upgrades to factory installed
CH530 control systems.
42
Range
Default Setting
Auto, Fixed
0–100%
Range
Default Setting
38–60 Hertz
38–60 Hertz
0–5%
Range
Default Setting
Not Applicable
Not Applicable
Not Applicable
Wye-Delta
Range
Default Setting
210–335
CVHE = 3, CVHF = 2
Range
Default Setting
1–30 Seconds
180–15000 Volts
0–700
0–2500 Amps
0–2000
15–100%
10–255 Seconds
6–64 Seconds
Shutdown, Transition
Shutdown
Exponential, Linear
Enable, Disable
Enable, Disable
20–1000 milliseconds
Enable, Disable
Enable, Disable
0–255 Seconds
0–100%
0–255 Seconds
Recommended Setting
Auto
20
Recommended Setting
60
38
1
Recommended Setting
Recommended Setting
275
Enter CPIM from Unit Nameplate
2
Enter from Unit Nameplate
Recommended Setting
3
460
Enter from Unit Nameplate
20
Enter from Unit Nameplate
500
Enter from Unit Nameplate
0
Choose Correct CT Meter Scale from
30
90
6
Linear
Enable
Disable
700
Enable
Enable
30
20
15
Auto
20
60
38
1
CVR
Non-Comm AFD
30
Table 23, p. 41
30
90
6
Shutdown
Linear
Disable
Disable
1000
Enable
Disable
60
20
15
AFDH-SVN02D-EN