3.2 Specifications of Outdoor unit Refrigerant Cycle Parts.
Model name
Motor type
Power supply
Output
Comp-
Pole
ressor
motor
Coil resistance
Compressor oil name
Amount of oil
Model name
Motor type
Power supply
Fan
Output
motor
Supply current
Pole
Inner over-load relay
High
Model name
pressure
Operating pressure
switch
Low
Model name
pressure
Operating pressure
switch
4-way valve
Compressor case heater
Pressure sensor
Discharge temperature sensor
Suction temperature sensor
Outdoor air temperature sensor
Pulse modulating valve (For bypass)
Pulse modulating valve
2-way valve
2-way valve
Model Name
(kW)
(P)
(Ω)
(cc)
(W)
(A)
(P)
(kgf/cm
(kgf/cm
MAR-M104HTM8-1-PE MAR-F104HTM8-1-PE
3-phase induction motor
380 – 415V, 3-phase, 50Hz
2/2 (Inverter side/Non-inverter side)
(Inverter side/Non-inverter side)
1-phase, induction motor
220 – 240V, 1-phase, 50Hz
20PS-B (Inverter side), 20PS-G (Non-inverter side)
2
G)
Operation 30, Reset 23
2
G)
Operation 0.25, Reset 1.5
CHV-0712, Coil AC240V
Model name: NTP-Q250TF-2
Output voltage: DC 0.5 – 4.5V
At 25°C = 50kΩ, 50°C = 17.9kΩ, 100°C = 3.35kΩ
At 0°C = 32.8kΩ, 25°C = 10kΩ, 50°C = 3.6kΩ
At 0°C = 32.8kΩ, 25°C = 10kΩ, 50°C = 3.6kΩ
EV18RC2, Coil DC 12V
NEV202DXF, Coil AC 240V
10
MG1300CW-20
7.5
1.49/2.51
NISSEKI RB68AF
7,000
STF-200-150C
150
1.12 ~ 1.44
6
OFF: 115 ± 5°C
20PS-1
AC 240V, 74W
Input voltage: DC 12V
EV23RC8, Coil DC
RP100-03, Coil AC

Hide quick links: