Download Print this page

Haier HPU-18C03/E1 Installation Manual page 5

Haier hpu-18c03/e1: user guide
Hide thumbs Also See for HPU-18C03/E1:

Advertisement

Installation Manual of Room Air Conditioner
Others
1. Power supply
Air conditioner must use an exclusive line(over 30A) and there is not power plug with this type,
the type of power supply wireHPU-18/24C03/E1 is 2.5mm
When installation air conditoner in a wet place, try to use a circuit breaker against Current
leakage.
For installation in other palces, use circuit breaker as far as possible.
2. Piping cutting and flaring
Be sure to carry out deburring after cutting with a pipe cutter.
Insert flaring tool to make a flare.
A
Correct
Installation inspection and test run:
Please operate unit according to this Manual.
Items to be checked during test run. Please made a ''
Are there any gas leakage?
How is insulation at piping connection carried out?
Are electric wires of indoor and outdoor unit firmly inserted into terminal block?
Is electric wiring of indoor and outdoor securely fixed?
Is drainage securely carried out?
Is earth line(grounding) securely connected?
Is power supply voltage abided by the code?
Is there any noise?
Is control display normal?
Is cooling operation normal?
Is room temp. regulator normal?
Flare tooling die
Lean Damage of flare
2
、HPU-18/24H03/E1 is 4.0mm
Pipe diameter
Liquid pipe
6.35mm(3/8")
Gas pipe
12.7mm(5/8")
Liquid pipe
9.52mm(3/8")
Gas pipe
15.88mm(5/8")
Incorrect
Crack
Partial
'' in ''
27
Size A (mm)
0.8 ~1.5
1.2 ~2.0
1.0 ~1.2
1.4 ~2.2
Too outside
''
2
.

Advertisement

loading

This manual is also suitable for:

Hpu-18h03/e1Hpu-24h03/e1Hpu-24c03/e1