The solar circuit pump does not work, although
the collector is considerably warmer than the
store.
Operating control
lamp of the controller
illuminated?
No current; check
yes
no
and replace fuse is
necessary and check
power supply.
Does the pump
start up in manual
operation?
yes
no
The adjusted tempe-
rature difference for
starting the pump is
too high; choose a
Is the pump current
value which makes
enabled by the cont-
more sense.
roller?
no
yes
Is the pump stuck?
Turn the pump shaft
using a screwdriver;
now passable?
Controller fuse o.k.?
Pump is defective -
yes
replace it.
no
Controller is defec-
tive - replace it.
Replace the fuse.
34
Stores cool down at night.
Collector circuit
pump runs during the
night?
no
yes
Collector tempera-
ture at night is higher
than the outdoor
temperature.
no
yes
Sufficient store
insulation?
yes
no
Insulation close
enough to the store?
yes
no
yes
Are the store con-
nections insulated?
yes
no
Warm water outflow
upwards?
no
no
yes
a
a
Does the warm water
circulation run for a
very long time?
no
Check controller
Circulation pump
and blocking valve
should be switched
off for 1 night; less
store losses?
Check the non-
return valves in the
flow and the return
yes
pipe for functional
efficiency.
Check the non-
return valve in warm
water circulation - o.k.
Increase insulation.
yes
Replace insulation or
The gravitation
increase it.
circulation in the
circulation line is
too strong; insert a
stronger valve in the
Insulate the connec-
non-return valve or an
tions.
electrical 2-port valve
behind the circulation
Change connection
pump; the 2-port valve
is open when the
and let the water flow
sidewards or through
pump is activated,
a siphon (down-
otherwise it is closed;
connect pump
wards); less store
losses now?
and 2-port valve
electrically in parallel;
no
yes
activate the circulation
again. Deactivate pump
o.k.
speed control!
Use the circulation
pump with timer and
switch-off thermos-
yes
tat (energy efficient
circulation).
Check whether the
pumps of the afterhea-
ting circuit run at night;
check whether the
non-return valve is
defective; problem
no
solved?
no
Further pumps which
are connected to the
solar store must also
no
be checked.
Clean or replace it.