ABB CoriolisMaster FCM2000 Commissioning Instructions page 48

Mass flowmeter
Hide thumbs Also See for CoriolisMaster FCM2000:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 35
Installation
Pos: 14.13 /Standard-Layout/Technische Daten / Datenblatt/Durchfluss/FCM2000/Elektrischer Anschluss/Profibus PA/FOUNDATION Fieldbus, Hilfsenergie des ME2 / MC2 (CI) @ 26\mod_1237379116796_3101.doc @ 248308 @ 5 @ 1
PROFIBUS PA/FOUNDATION Fieldbus, supply power for ME2/MC2
1+
2-
L
N
1
Fig. 8
1 Supply power
Line voltage: U
100 ... 230 V AC, frequency 50/60 Hz,
AC
terminals L, N,
Low voltage: U
24 V, frequency 50/60 Hz, terminals 1+, 2-;
AC
U
24 V
DC
2a PROFIBUS PA design according to IEC 61158-2 (Profile 3.0)
U = 9 ... 32 V
I = 14 mA (normal operation)
I = 26 mA (in the event of an error/FDE)
Terminals: 97/98
You can find a connection example in the operating instructions
under "Connecting via M12 plug".
Pos: 14.14 /Standard-Layout/======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830 @ @ 1
14 - EN
97 98
3
2
2-
1+
N
L
97 98
3
2
1
CoriolisMaster FCM2000
MC23
MC27
3
3
ME26
MC26
3
3
ME21
3
MC21
3
2b FOUNDATION Fieldbus design according to IEC 61158-2
U = 9 ... 32 V
I = 14 mA (normal operation)
I = 26 mA (in the event of an error/FDE)
Terminals: 97/98
You can find a connection example in the operating instructions
under "Connecting via M12 plug".
3 "PA" equipotential bonding. The precise position of the ground
terminals may vary according to the device type. However, the
position is appropriately labeled in each case. When connecting
transmitter ME2 to flowmeter sensor MC26, transmitter ME2
also has to be connected to "PA".
G00816
CI/FCM2000-EN