DISTRIBUTION UNIT
Type 138- -118
1 Description
2 Installation
3647.DOC010302 Edition:
Revision:
Revision:
Sept. 05, 2005
Nov. 28, 2005
Feb. 17, 2006
Raytheon Anschütz GmbH
Postfach 1166
D - - 24100 Kiel
Germany
Tel +49- -4 31- -30 19- -0
Fax +49- -4 31- -30 19- -501
Email Service@raykiel.com
www.raytheon- -anschuetz.de

Advertisement

Table of Contents
loading

Summary of Contents for Raytheon Anschütz 138-118

  • Page 1 Raytheon Anschütz GmbH Postfach 1166 D - - 24100 Kiel Germany Tel +49- -4 31- -30 19- -0 Fax +49- -4 31- -30 19- -501 Email Service@raykiel.com www.raytheon- -anschuetz.de DISTRIBUTION UNIT Type 138- -118 1 Description 2 Installation 3647.DOC010302 Edition: Sept.
  • Page 2 Weitergabe sowie Vervielfältigung dieser Unterlage, Verwertung und Copying of this document, and giving it to others and the use or Mitteilung ihres Inhaltes nicht gestattet, soweit nicht ausdrücklich communication of the contents thereof, are forbidden without express zugestanden. Zuwiderhandlungen verpflichten zu Schadenersatz. authority.
  • Page 3: Table Of Contents

    Distribution Unit DISTRIBUTION 138- -118 UNIT CONTENTS Page Declaration of Conformity ..........General .
  • Page 4 Distribution Unit 138- -118 Maintenance and Repair ..........Error indication .
  • Page 5 Distribution Unit DISTRIBUTION 138- -118 UNIT Edition: Sept. 05, 2005 3647.DOC010302...
  • Page 6 Distribution Unit 138- -118 3647.DOC010302 Edition: Sept. 05, 2005...
  • Page 7 Distribution Unit DISTRIBUTION 138- -118 UNIT Caused by technical progress the PC--Boards of the Gyro Compass are changed. Due to that some pictures and/or procedures have been changed. Respective changes are marked with “E10”. Safety instructions Caution: Installation, maintenance and repair work must be carried out only by properly trained and qualified staff with a good knowledge of national equipment safety regulations.
  • Page 8 Distribution Unit 138- -118 3647.DOC010302 Edition: Sept. 05, 2005...
  • Page 9: General

    Distribution Unit DISTRIBUTION 138- -118 UNIT General The Distribution Unit 138--118 consists of an aluminium casting in which 2 printed circuit board are integrated. -- I/O--PCB -- Interface PCB. At the bottom of the casting there are 40 cable inlets for connecting repeaters, gyros and other heading receivers and sensors.
  • Page 10: Can Bus

    Distribution Unit 138- -118 CAN-Bus (CAN = Controller Area Network) The CAN bus is a Multi-Master-Bus allowing the CAN bus connection of all devices and systems regardless of their task and function. This means that any number of devices can be connected. These de- vices must be designed for CAN bus technology.
  • Page 11: Technical Data

    Distribution Unit DISTRIBUTION 138- -118 UNIT Technical Data 1.2.1 Mechanical Data see Dimensional Drawing “Distribution Unit 138--118.HP005” Equipment category: IP22 1.2.2 Electrical Data Supply Voltage: 18VDC..40VDC Max. Current: (2 Gyros and 8 Repeaters) Input: --Spd--Log ⎮ Pulslog --NMEA GPS ⎮ NMEA log --Log --CAN Bus --DV Bus...
  • Page 12: Information About Led's, Push Buttons, Switches, Plugs And Connectors Of The Integrated Pcb's

    Distribution Unit 138- -118 Information about LED‘s, push buttons, switches, plugs and connectors of the integrated PCB‘s 1.3.1 Interface PCB and I/O PCB 4 5 6 7 8 9 10 11 12 13 14 Fig.2: Interface PCB (138--118.100) 3647.DOC010302 Edition: Sept. 05, 2005...
  • Page 13 Distribution Unit DISTRIBUTION 138- -118 UNIT Designation at the Interface Remark Fig.2/1 Terminal Board L1 of the Connection of supply voltages Distribution Unit for the distribution unit itself and for connected gyros, operator unit and heading receivers. Fig.2/2 LED H1 +5VDC DC/DC--Converter for CAN--Bus and Course Bus Fig.2/3...
  • Page 14 Distribution Unit 138- -118 5 6 7 Fig.3:I/O PCB (138--118.101) 3647.DOC010302 Edition: Sept. 05, 2005...
  • Page 15 Distribution Unit DISTRIBUTION 138- -118 UNIT Designation at the I/O PCB Remark Fig.3/1 Connector B1 Connection to the Interface PCB Fig.3/2 LED H30 35V DC Voltage (Step) Fig.3/3 Push Button B40 Processor Reset Fig.3/4 LED +5V5 +5VDC for RoT--Conversion Fig.3/5 LED +5V4 +5VDC galvanically separated supply voltage...
  • Page 16 Distribution Unit 138- -118 Designation at the I/O PCB Remark Fig.3/21 Plug B28 Output Channel 6 with 3 LED‘s blue = NMEA 2 green = NMEA 1 red = Course bus Fig.3/22 Plug B27 Output Channel 5 with 3 LED‘s blue = NMEA 2 green = NMEA 1 red = Course bus...
  • Page 17 Distribution Unit DISTRIBUTION 138- -118 UNIT Designation at the I/O PCB Remark Fig.3/46 Plug B12 with LED H3 Status--Signal with indication “SENSORALARM G1” Fig.3/47 Plug B22 with LED H13 General Alarm RESET Fig.3/48 Plug B19 with LED H10 Status--Signal with indication “GYRO SELECTED”...
  • Page 18: Terminal Board, Interface Pcb And I/O Pcb (E10)

    Distribution Unit 138- -118 1.3.2 Terminal Board, Interface PCB and I/O PCB (E10) Fig.4: Terminal board L1 Designation Remark Fig.4/1 Terminal board L1 Connection for the supply voltage for the Distribution Unit itself, for the con- nected compasses, the Operator Unit and the heading receivers.
  • Page 19 Distribution Unit DISTRIBUTION 138- -118 UNIT 12 13 14 15 16 17 18 Fig.5: Interface PCB (138--118.100 E10) Designation at the Remark Interface PCB E10 Fig.5/1 Plug B7 CAN2--Bus Fig.5/2 Switch B32 Resistor CAN2--Bus Fig.5/3 LED H2 +5V DC CAN1--Bus Fig.5/4 LED H3 +5V DC CAN2--Bus...
  • Page 20 Distribution Unit 138- -118 Designation at the Remark Interface PCB E10 Fig.5/9 Terminal board L1 of the Supply voltage +24V DC for the Interface PCB Interface PCB Fig.5/10 Switch B2 Course bus/NMEA (test purpose only) Fig.5/11 DIP--Switch B20 Einstellungen für die Distribution Unit Fig.5/12 Push button B23 Mode selection together with DIP-- Switch B20...
  • Page 21 Distribution Unit DISTRIBUTION 138- -118 UNIT 6 7 8 9 10 11 see Fig.8 see Fig.7 see Fig.9 see Fig.10 Fig.6: I/O PCB (138--118.101. E10) Designation at the Remark I/O PCB E10 Fig.6/1 Switch B41 Test purpose only. Has to be always in closed position.
  • Page 22 Distribution Unit 138- -118 B 39 Fig.7: I/O PCB (138--118.101. E10) Designation at the Remark I/O PCB E10 Fig.7/1 LED H60 not used Fig.7/2 Switch B42 not used Fig.7/3 Push button B38 no function, not used Fig.7/4 Switch B39 no function, not used Fig.7/5 Push button B37 no function, not used...
  • Page 23 Distribution Unit DISTRIBUTION 138- -118 UNIT Fig.8: I/O PCB (138--118.101. E10) Designation at the Remark I/O PCB E10 Fig.8/1 Plug B16 with LED H7 Status--signal--connection with indica- tion “MONITORALARM GYRO/TMC” Fig.8/2 Plug B19 with LED H10 Status--signal--connection with indica- tion “GYRO SELECTED” Fig.8/3 Plug B22 with LED H13 General Alarm RESET...
  • Page 24 Distribution Unit 138- -118 Designation at the Remark I/O PCB E10 Fig.8/9 Plug B14 with LED H5 Status--signal--connection with indica- tion “SENSORALARM G3/GPS” Fig.8/10 Plug B12 with LED H3 Status--signal--connection with indica- tion “SENSORALARM G1/GPS” Fig.8/11 Plug B15 with LED H6 Status--signal--connection with indica- tion “SENSORALARM TMC”...
  • Page 25 Distribution Unit DISTRIBUTION 138- -118 UNIT Fig.9: I/O PCB (138--118.101. E10) Designation at the Remark I/O PCB E10 Fig.9/1 Plug B35 Connection of Course bus to the I/O PCB. Fig.9/2 Plug B9 Connection of Step--output. Fig.9/3 Fuse E11 Protection (0,25A, slow) 35V DC of the Step--output at plug B9.
  • Page 26 Distribution Unit 138- -118 5 (Channel 4) (Channel 8) 4 6 (Channel 3) (Channel 7) 3 7 (Channel 2) (Channel 6) 2 8 (Channel 1) (Channel 5) 1 (Channel 9) (Channel 11) (Channel 10) (Channel 12) Fig.10: I/O PCB (138--118.101. E10) Designation at the Remark I/O PCB E10...
  • Page 27 Distribution Unit DISTRIBUTION 138- -118 UNIT Designation at the Remark I/O PCB E10 Fig.10/9 Plug B 34 Output channel 12 to connect repeater without LED H 57 (red) supply voltage. LED H 56 (green) Connection and indication of the adjusted data LED H 55 (blue) format.
  • Page 28: Installation Of The Distribution Unit

    Distribution Unit 138- -118 Installation of the Distribution Unit General remarks Caution When establishing cable connections ensure that the cables are disconnected from the power supply. It is essential to ensure that all cables are disconnected from the power supply, if necessary measure the voltage beforehand and/or disconnect the relevant distributor.
  • Page 29 Distribution Unit DISTRIBUTION 138- -118 UNIT -- Push the counterpart of the earthing insert as far as the end of the cable shield. -- Push the earthing insert cone below the shielding against the counterpart. Observe a shared evenly distribution of the shielding via the cone (see Fig.12). Wall and DIN socket Earthing insert -- Cone...
  • Page 30 Distribution Unit 138- -118 Option: Cable connection with a screen clamp Attach the angle with cross slotted screws below the respective cable inlet at the hous- ing. (angle and screws are part of the in- stallation kit). Strip off the cable according to section 2.1. The screen must be led for appr.
  • Page 31: General Information About Establishing An Earth Connection

    Distribution Unit DISTRIBUTION 138- -118 UNIT 2.1.1 General information about establishing an earth connection In order to comply with the stringent EMC requirements, please abide by the information given below regarding cable connections. Use the cable types specified. Earth connections should be connected to the gyro compass and to the junction box. It is essential to ensure that these connections have a common reference to the ship’s earth.
  • Page 32: Installation

    Distribution Unit 138- -118 Installation The distribution unit has to be mounted according to the dimensional drawing 138--118.HP005. The front cover should be removable. Please note the comment depending the internal protection at the dimensional drawing. 2.2.1 Installation of the options For installations of the options, as there are “Additional Output Box”...
  • Page 33 Distribution Unit DISTRIBUTION 138- -118 UNIT The installation of the power supply (AC/DC--Converter) should only be per- formed by an experienced electrician. The supply voltage has to be engineered as a low--security-- voltage according to SELV. Plastic cover Adhesive cable tie mounts Tie wrap Fig.15...
  • Page 34: Connections

    Distribution Unit 138- -118 Connections At a Distribution Unit with DV--bus application no con- nections for speed and/or position should be made. CAN--bus Example: Distribution Unit DV--bus NMEA Position/Speed For example Log Direction/Speed Nautoconning All connections to terminal boards and plugs have to be made according appended drawings.
  • Page 35: Connection Of Dv--Bus

    Distribution Unit DISTRIBUTION 138- -118 UNIT 2.3.2 Connection of DV- -bus Connections have to be made according section 2.1 and appended drawings. Interface PCB: Anschlußklemme L2 Interface PCB (E10): Anschlußklemme B17 Fig.16: DV--bus connection Function Terminal board L2 Plug B17 (E10) Screen A Core A Core A...
  • Page 36: Switching On The Distribution Unit

    Distribution Unit 138- -118 Switching On the Distribution Unit After connecting the supply voltage, the Distribution Unit is switched on. All direct connected devices (as there are compass, and repeater with supply voltage) to the Distribution Unit are supplied with operating voltage as well. There is no separate switch for the Distribution Unit.
  • Page 37: Setting Of Jumpers And Adjusting The Dip--Switches

    Distribution Unit DISTRIBUTION 138- -118 UNIT Setting of Jumpers and Adjusting the DIP- -Switches Setting of Jumpers Basically 3 jumpers have to be awarded. These jumpers are the terminators (resistors which terminate the CAN--bus and the DV-- bus). Is a distribution Unit used as an so called “end--device” within a CAN--bus and DV--bus application, all jumpers have to be set.
  • Page 38: Activation The Termination Resistors By Switches (E10)

    Distribution Unit 138- -118 Jumper B1 Jumper B4 Programming DV--bus terminator DV--bus (never set while operation) Jumper between 1--2 has to be set, if the distribution unit is an end--device within a DV--bus application Fig.18: DV--bus terminator 4.1.1 Activation the termination resistors by switches (E10) Basically 3 switches have to be awarded.
  • Page 39 Distribution Unit DISTRIBUTION 138- -118 UNIT DV--bus CAN--bus Fig.19: Switches to activate the terminators Switch B32 in position ON activates the terminator for CAN1--bus Switch B31 in position ON activates the terminator for CAN2--bus Switch B4 in position ON activates the terminator for DV--bus Edition: Sept.
  • Page 40: Setting Of Dip--Switches

    Distribution Unit 138- -118 Setting of DIP- -Switches 4.2.1 Setting of DIP- -Switches for DV- -bus application DIP--Switch B24 Fig.20: DIP--Switch for DV--bus application All DIP--Switches of B24 have to be switched to position “OFF”. These switches are actually not used. 3647.DOC010302 Edition: Sept.
  • Page 41: Setting Of Dip--Switches For Can--Bus

    Distribution Unit DISTRIBUTION 138- -118 UNIT 4.2.2 Setting of DIP- -Switches for CAN- -bus (B23) (B22) DIP--Switch 1 (B20) DIP--Switch 8 Display DIP--Switch Fig.21: DIP--Switches, display and push buttons to select and adjust different operation modes 1 = DIP--Switch B20 with 8 single switches 2 = Push button B23 to select the modes within the respective DIP--Switch settings 3 = Display 4 = Push button B22 to set selected mode...
  • Page 42: General Information In Use Of The Dip--Switch And Push Buttons

    Distribution Unit 138- -118 4.2.3 General information in use of the DIP- -Switch and push buttons The normal operation of the all DIP--Switches is the “DOWN”--position. This means the respective switch is closed. In the upper position the respective switch is open and by this, a mode can be selected and adjusted.
  • Page 43: Setting Of Can Bus Address

    Distribution Unit DISTRIBUTION 138- -118 UNIT 4.2.3.2 Setting of CAN Bus address Each device within a CAN bus application has to be identified with an address. This address must not be twice within this application (bus--conflict)!! The CAN bus address is already adjusted by the manufacturer. Below mentioned procedure to adjust the address is only necessary if a second Distribu- tion Unit should be connected.
  • Page 44 Distribution Unit 138- -118 Operate push button B21 “RESET Processor” (Fig.2/6) to ac- knowledge Switch OFF an ON again voltage supply to the Distribution Unit, by this the changed address is set. Below mentioned table shows the CAN bus addressees for one or several Distribution Units.
  • Page 45: Adjustment Of The 8 Output Channels (12 Output Channels --> E10)

    Distribution Unit DISTRIBUTION 138- -118 UNIT 4.2.3.3 Adjustment of the 8 output channels (12 output channels - -> E10) Each of the 8 (12) output channels can be set to 3 different interfaces. These interfaces are: Course bus, NMEA1 and NMEA2. With the formats NMEA1 and NMEA2 to different configurations can be adjusted, these configurations become active after selection (to the respective output channel).
  • Page 46 Distribution Unit 138- -118 Number of operations of Display Interface format Plug at the PCB the push button B23 after switching of switches 1, 2 and 3 Plug B23 Chn1 (B20) into the upper position HSEr Course bus (red LED) nME1 NMEA1 (green LED) nME2...
  • Page 47: Adjustment Of Nmea Formats

    Distribution Unit DISTRIBUTION 138- -118 UNIT 4.2.3.4 Adjustments of NMEA Formats The Distribution Unit can provide for each output one of three different data formats (Course bus, NMEA1 and NMEA2). Selected format can be recognized by the respective LED colour. The content of the course bus format cannot be changed, but both NMEA formats can be adjusted concerning to telegram-- type and repetition rate.
  • Page 48 Distribution Unit 138- -118 Meaning of the telegram abbreviations: HEHDT = Heading corrected, from a Gyro compass HCHDT = Heading corrected, from a Magnetic compass HCHDG = Heading uncorrected from a Magnetic compass TIROT = Turn rate from a turn rate sensor HEROT = Turn rate from a Gyro compass -- By each operation of push button B23 another format is selected and displayed.
  • Page 49 Distribution Unit DISTRIBUTION 138- -118 UNIT Procedure for NMEA2: DIP--Switch B20 OPEN Fig.25: DIP--Switch position to adjust the NMEA2 interface -- Switch 2 of the DIP--Switch into the upper position. Operation of push Display Interface button B23 after switching (B20) switch 2 into the upper position nME2...
  • Page 50 Distribution Unit 138- -118 -- By each operation of push button B23 another format is selected and displayed. -- Each adjusted format has to be set wit push button B22 (right of the display). The set format information blinks at the display. -- After adjustment of all connected channels, the switch 2 has to be set into lower position.
  • Page 51: Adjustment Of Nmea Formats (E10)

    Distribution Unit DISTRIBUTION 138- -118 UNIT 4.2.3.5 Adjustment of NMEA Formats (E10) The Distribution Unit can provide for each output one of three different data formats (Course bus, NMEA1 and NMEA2). Selected format can be recognized by the respective LED colour. The content of the course bus format cannot be changed, but both NMEA formats can be adjusted concerning to telegram-- type and repetition rate.
  • Page 52 Distribution Unit 138- -118 Meaning of the telegram abbreviations: CY and cY means “Cycle” = 1Hz CY10 = 10Hz CY50 = 50Hz HEHDT = Heading corrected, from a Gyro compass HCHDT = Heading corrected, from a Magnetic compass HCHDG = Heading uncorrected from a Magnetic compass TIROT = Turn rate from a turn rate sensor HEROT = Turn rate from a Gyro compass -- By each operation of push button B23 another format is selected and displayed.
  • Page 53 Distribution Unit DISTRIBUTION 138- -118 UNIT Procedure for NMEA2: DIP--Switch B20 OPEN Fig.27: DIP--Switch position to adjust the NMEA2 interface -- Switch 2 of the DIP--Switch into the upper position. Number of oper- Display Baudrate Interface ations of push button after switching switch 2 (B20) into the upper nME1...
  • Page 54 Distribution Unit 138- -118 -- By each operation of push button B23 another format is selected and displayed. -- Each adjusted format has to be set wit push button B22 (right of the display). The set format information blinks at the display. -- After adjustment of all connected channels, the switch 1 has to be set into lower position.
  • Page 55: Left Blank

    Distribution Unit DISTRIBUTION 138- -118 UNIT 4.2.3.6 Left blank Edition: Nov. 28, 2005 3647.DOC010302...
  • Page 56: Scaling Of Rot Output

    Distribution Unit 138- -118 4.2.3.7 Scaling of RoT Output For the RoT--output an adjustment of the turn rate has to be performed. DIP--Switch B20 OPEN Fig.28: DIP--Switch position to adjust the turn rate Procedure: -- Switch 3 of the DIP--Switch into the upper position. Operation of push button Display Rate of Turn...
  • Page 57: Selection Of Magnetic Compass

    Distribution Unit DISTRIBUTION 138- -118 UNIT 4.2.3.8 Selection of magnetic compass DIP--Switch B20 OPEN Fig.29: DIP--Switch position to adjust application with Magnetic compass With this adjustment it is to determine if a magnetic compass is connected to this ap- plication. -- Switch 4 of the DIP--Switch (B23) into the upper position.
  • Page 58: Displaying Heading Or Speed Information

    Distribution Unit 138- -118 4.2.3.9 Displaying heading or speed information This setting allows to check the heading information of selected sensor, the speed in- formation of the Log or information about supply voltages. DIP--Switch B20 OPEN Fig.30: DIP--Switch position to adjust output of heading and sped values Procedure: Operation of push Display...
  • Page 59: Switching Off The Distribution Unit

    Distribution Unit DISTRIBUTION 138- -118 UNIT Switching OFF the Distribution Unit By switching OFF the supply voltage, the distribution unit is switched OFF. All direct connected devices to the Distribution Unit, as there are compass and repeaters with supplied voltage are switched off as well. A separate switching off of the Distribution Unit is not possible.
  • Page 60: Adjustments

    Distribution Unit 138- -118 Adjustments Adjustment of magnetic sonde This adjustment should be performed only be well trained technicians. Necessary tools and measuring instruments -- Screw driver to adjust potentiometer -- Voltmeter -- Iron tool to influence the magnetic sonde TP12 TP11 R155...
  • Page 61 Distribution Unit DISTRIBUTION 138- -118 UNIT Adjustment after installation of the magnetic sonde (see Fig.31) The Distribution Unit is in operation. Magnetic sonde is installed and connected to the Distribution Unit. -- Switch the switches 6,7 and 8 of the DIP switch B20 into the upper position “OPEN”). -- Operate push button B22 until the display shows “MAGS”.
  • Page 62 Distribution Unit 138- -118 Maintenance and Repair The Distribution Unit is maintenance free. A repair is constrained to the exchange of the PCB‘s: I/O PCB Identnumber 138--118.101 138--118.101 E10 Interface PCB Identnumber 138--118.103 138--118.100 E10 Operation during a repair can only be performed when the CAN--bus is terminated.
  • Page 63 Distribution Unit DISTRIBUTION 138- -118 UNIT Operate the push button B23 during an error is displayed. Two different information can be displayed after that. Fig.33: Display to determine an error Error indication “PCB0” points to a faulty Interface PCB, an error indication “PCB1” points to a faulty I/O PCB.
  • Page 64 Distribution Unit 138- -118 Functional description of DIP switch settings in the Service mode All data stated below should be selected and read out for servicing purposes only. In standard operation the following data has no significance. The Service Mode is switched ON with DIP--Switches 6+,7 and 8 into the upper position. DIP--Schalter B20 OPEN Seq.
  • Page 65 Distribution Unit DISTRIBUTION 138- -118 UNIT Seq. Indications Comments, Notes Corr = Corrected course (course taking SEC into account) DIP--Switch B20: positions 6,7 and 8 GYr1 = Displays corrected heading for Gyro compass 1 DIP--Switch B20: positions 6,7 and 8 If there is no “Gyro 1”...
  • Page 66 Distribution Unit 138- -118 Seq. Indications Comments, Notes Addr = Displays CAN--bus address for Gyro Compass 1 DIP--Switch B20: positions 6,7 and 8 If there is no “Gyro 1” connected. GYr2 = Displays corrected heading for Gyro compass 2 DIP--Switch B20: positions 6,7 and 8 If there is no “Gyro 2”...
  • Page 67 Distribution Unit DISTRIBUTION 138- -118 UNIT Seq. Indications Comments, Notes Addr = Displays CAN--bus address for Gyro Compass 2 DIP--Switch B20: positions 6,7 and 8 If there is no “Gyro 2” connected. GYr3 = Displays corrected heading for Gyro compass 3 DIP--Switch B20: positions 6,7 and 8 If there is no...
  • Page 68 Distribution Unit 138- -118 Seq. Indications Comments, Notes Addr = Displays CAN--bus address for Gyro Compass 3 DIP--Switch B20: positions 6,7 and 8 If there is no “Gyro 3” connected. MAGS = Displays heading of magnetic compass DIP--Switch B20: positions 6,7 and 8 No heading available or heading of mag- netic compass faulty...
  • Page 69 Distribution Unit DISTRIBUTION 138- -118 UNIT Seq. Indications Comments, Notes MAGC = Displays corrected heading or magnetic compass Deviation and variation included DIP--Switch B20: positions 6,7 and 8 No heading available or heading of mag- netic compass faulty No magnetic compass connected MISS = Displays Variation value DIP--Switch B20:...
  • Page 70 Distribution Unit 138- -118 Seq. Indications Comments, Notes dEvI = Displays deviation value Value out of an internal table, respective to the actual magnetic compass heading DIP--Switch B20: positions 6,7 and 8 Mrot = Displays Rate of Turn of the magnetic compass DIP--Switch B20: positions 6,7 and 8 Display : Degree per minute...
  • Page 71 Distribution Unit DISTRIBUTION 138- -118 UNIT Seq. Indications Comments, Notes SCi = Serial Interface, telegram traffic on serial interface DIP--Switch B20: positions 6,7 and 8 Contents alternate Digit 2: GPS--Interface Digit 1: NMEA--Interface (Speed in) Digit 0: Sum of all telegrams on both interfaces UART 1 (GPS)
  • Page 72 Distribution Unit 138- -118 Seq. Indications Comments, Notes SrC.S = Source of Speed Information Data about the source providing the speed value DIP--Switch B20: positions 6,7 and 8 Display options: PULS = Puls log* = Speed over ground = Speed through water (vtG and vhW corresponds to NMEA 0183) also shown in DV--bus application...
  • Page 73 Distribution Unit DISTRIBUTION 138- -118 UNIT Seq. Indications Comments, Notes vtG.S = Speed from GPS--telegram (speed over ground) DIP--Switch B20: positions 6,7 and 8 No telegram, DV--bus application or faulty data from GPS (vTg--telegram) vtG.h = Course value from GPS telegram DIP--Switch B20: positions 6,7 and 8 No telegram, DV--bus application,...
  • Page 74 Distribution Unit 138- -118 Seq. Indications Comments, Notes vhw = Speed value in knots from NMEA telegram (speed through water) DIP--Switch B20: positions 6,7 and 8 No telegram, DV--bus applica- tion, or faulty serial speed data (vHw--telegram) SPd.A = Speed in knots (actual value) (or value from DV--bus) The speed for which the source has been selected, is displayed.
  • Page 75 Distribution Unit DISTRIBUTION 138- -118 UNIT Seq. Indications Comments, Notes PoS = Position -- latitude in degrees DIP--Switch B20: positions 6,7 and 8 Automatic latitude from GPS or actual latitude from the DV bus No latitude data available (GPS defective) or DV--bus application ASPd = Alarm Speed DIP--Switch B20:...
  • Page 76 Distribution Unit 138- -118 Seq. Indications Comments, Notes PoSn = Latitude value derives from automatic latitude input. Indicated in degrees DIP--Switch B20: positions 6,7 and 8 Actual latitude (or manual set latitude value) or automatic latitude from the DV bus In case of a fault, the last actual latitude is displayed.
  • Page 77 Distribution Unit DISTRIBUTION 138- -118 UNIT Seq. Indications Comments, Notes nAn1 = 1st table for NMEA--requests DIP--Switch B20: positions 6,7 and 8 L = telegram type GLL G = telegram type GGA t = telegram type VTG h = telegram type VHW 1st digit = number of L--types 2nd digit = number of G--types 3rd digit = number of t--types...
  • Page 78 Distribution Unit 138- -118 Seq. Indications Comments, Notes nSGG = NMEA--telegram (strings of the GGA--telegram) DIP--Switch B20: positions 6,7 and 8 Number of ASCII--characters per telegram 0000 = no telegram The number of operations depends on the number of characters. (1 display content = max.
  • Page 79 Distribution Unit DISTRIBUTION 138- -118 UNIT Seq. Indications Comments, Notes nSGL = NMEA--telegram (String of the GLL--telegram) DIP--Switch B20: positions 6,7 and 8 Example Length of the telegram = 44 ASCII--characters Edition: Sept. 05, 2005 3647.DOC010302...
  • Page 80 Distribution Unit 138- -118 Seq. Indications Comments, Notes nSGL = NMEA--telegram (Strings of the GLL--telegram) cont. DIP--Switch B20: positions 6,7 and 8 Checksum 3647.DOC010302 Edition: Sept. 05, 2005...
  • Page 81 Distribution Unit DISTRIBUTION 138- -118 UNIT Seq. Indications Comments, Notes nSGL = NMEA--telegram (Strings of the GLL--telegram) cont. DIP--Switch B20: positions 6,7 and 8 With the 1st operation of the contact switch B23, the number of ASCII--characters is displayed. If the display shows “0000”, no telegram--output took place. With every further operation of contact switch, 4 consecutive ASCII--characters are displayed.
  • Page 82 Distribution Unit 138- -118 Seq. Indications Comments, Notes nShw = NMEA--telegram (Strings of the VHW--telegram) DIP--Switch B20: positions 6,7 and 8 Number of ASCII--characters per telegram 0000 = no telegram The number of operations depends on the number of characters. (1 display content = max.
  • Page 83 Distribution Unit DISTRIBUTION 138- -118 UNIT Seq. Indications Comments, Notes nSbw = NMEA--telegram (String of the VBW--telegram) DIP--Switch B20: positions 6,7 and 8 Number of ASCII--characters per telegram 0000 = no telegram The number of operations depends on the number of characters. (1 display content = max.
  • Page 84 Distribution Unit 138- -118 Seq. Indications Comments, Notes Development only! SCI . = Serial Communication Interface NMEA Log/ GPS input) DIP--Switch B20: positions 6,7 and 8 The content of the two digits is during a data transfer unrecognisable. Just the digits 1 and 0 are vis- (16)
  • Page 85 Distribution Unit DISTRIBUTION 138- -118 UNIT Seq. Indications Comments, Notes AAdd = Alarm address of a defective Gyro compass DIP--Switch B20: positions 6,7 and 8 0000 → no faulty Gyro otherwise the CAN address. dUin = Software version of the CAN--bus processor of the Interface PCB DIP--Switch B20: positions 6,7 and 8 doUt = Software version of the I/O--PCB of the Distribution Unit...
  • Page 86 Distribution Unit 138- -118 Seq. Indications Comments, Notes dubS =Software version of the DV--bus processor of the Interface PCB DIP--Switch B20: positions 6,7 and 8 UTC = Time of *ZDA--Telegram DIP--Switch B20: positions 6,7 and 8 Hours Minutes Seconds Month Year With this signal the time for a connected course printer is synchronised.
  • Page 87 Distribution Unit DISTRIBUTION 138- -118 UNIT Table of DIP- -switch functions 8.1.1 Adjustments DIP-- Step Display Function Push but- Push but- switch ton B23 ton B22 (left) (right) 20 (ad- CAN--bus address setting of Distribution Unit. upwards down- dress) Perform processor reset with B21 after chang- wards ing address MAGn...
  • Page 88 Distribution Unit 138- -118 DIP-- Step Display Function Push but- Push but- switch ton B23 ton B22 (left) (right) --ro-- RoT output scaling choose Select for 30°/minute choose r100 Select for 100°/minute choose r300 Select for 300°/minute choose Select for analog heading output choose 8.1.2 Adjustments E10...
  • Page 89 Distribution Unit DISTRIBUTION 138- -118 UNIT DIP-- Step Display Function Push but- Push but- switch ton B23 ton B22 (left) (right) 1+2+3 Chn1 Output channels 1--8 data selection choose HSEr Select for heading serial (LED red) choose nME1 Select for NMEA, 1/sec (LED green) choose nME2 Select for NMEA, 10/sec (LED blue)
  • Page 90 Distribution Unit 138- -118 8.1.3 Displays DIP-- Step Display Function Push but- Push but- Switch ton B23 ton B22 (left) (right) Sen1 Heading value of Sensor 1 choose display Sen2 Heading value of Sensor 2 choose display Sen3 Heading value of Sensor 3 choose display Sen4...
  • Page 91 Distribution Unit DISTRIBUTION 138- -118 UNIT DIP-- Step Display Function Push but- Push but- Switch ton B23 ton B22 (left) (right) tINE Time since activating SEC display choose Display serial communication interface display choose SGAd CAN--bus address of selected sensor display choose AAdd...
  • Page 92 Distribution Unit 138- -118 3647.DOC010302 Edition: Sept. 05, 2005...
  • Page 93 Distribution Unit Ersatzteilkatalog Type 138--118.NG001 SPARE PARTS ANSCHÜTZ CATALOGUE Zeichnungs.Nr. Lager--Nr. Benennung Designation Stck. Herst.--Code Versorgungs--Nr. Pos. Stock--No. Part--No. Qty. MFRC 138--118.103 AT Interface PCB, recond D2865 3609431 Interface PCB, AT 3609430 138--118.101 AT D2865 I/O PCB, AT I/O PCB, recond T 1 A L 250 V 1.762017 G--Sicherungseinsatz...
  • Page 94 left blank...