Installation Sequence; Installing The Gateway And Power Supply Unit - Viessmann WAGO 750-8212/000-100 Installation And Service Instructions For Contractors

Bms communication with heating systems via bacnet, bacnet/ip gateway
Table of Contents

Advertisement

Process overview
Step
1
Install the gateway and power supply unit.
2
Establish the CAN bus connection.
3
Connect the plug-in attachment.
4
Establish the connection to BACnet.
5
Connect the gateway to the power supply unit
6
Power supply
7
Commission the gateway.

Installing the gateway and power supply unit

The gateway and power supply unit are suitable for
mounting on top-hat rails in control panels:
TS 35 to EN 50 022: 35 x 15 and 35 x 7.5.
!
Please note
Incorrect ambient conditions and installation
locations may impair data transfer and cause
damage to the gateway.
The gateway with its components is an open
device with IP rating IP 20. It should only be
mounted in enclosures, cabinets or in electrical
operating rooms.
Ambient conditions during operation
Permissible ambient temperature: 0 to 40 °C
Permissible relative humidity:
0 to 39 °C:
95 %
40 °C:
50 %
No direct sunlight
Requirements for the enclosure
Material
Min. dimensions
(width x height x depth)
Protective conductor
Flammability class
Grounding
IP rating
Top-hat rail mounting
!
Sheet steel
200 x 200 x 120 mm
Connect the enclosure to the protec-
tive conductor.
Enclosure and top-hat rail:
Depending on phase conductor
cross-section with min. 2.5 mm
Installed at a height of up to 1.60 m: IP 20D
Installed at a height of 1.61 m or higher: IP 20B
TS 35 to EN 50022
Length: Min. 190 mm

Installation sequence

Responsibility
Contractor
Contractor
Contractor
IT expert/system integrator
Electrician
Electrician
IT expert/system integrator
Please note
Operation by unauthorized persons may result
in damage to the system.
Access to the gateway must only be possible for
authorized specialists with a key or tool.
Plastic
278 x 278 x 130 mm
Connect the top-hat rail to the protec-
tive conductor via a protective conduc-
tor terminal.
Min. flammability class V-1 according
to EN 62368-1 or EN 60950-1
Top-hat rail:
Depending on phase conductor cross-
2
section with min. 2.5 mm
Page
9