INSTALLATION DIMENSIONS:

Applies to installation into non-flammable panels.
Minimum cavity dimensions (H x W x D): . 512 x 791 x 462 mm
A fireplace insert must never be tightly inserted into a cavity, as steel expands when
heated.
There must be a minimum convection air intake of 400 cm² underneath the stove and
600 cm² above it. The minimum convection-air areas above and below the stove can
be distributed over several holes.
Distance
Distance from convection grate to flammable ceiling
1276505
Visio Uniq - Hulmål
Distance from lower door edge to flammable floor
15 - EN
INSTALLATION DIMENSIONS
Dimensions,
mm
250
400
Convection air
Minimum
600 cm²
Minimum
400 cm²
A