Fault Table, Electromechanical Control; Start-Up After Rectification Of Fault - Kampmann TIP Assembly, Installation And Operating Instructions

Table of Contents

Advertisement

Fault
Unit too loud

11.2 Fault table, electromechanical control

Fault
EC fan does not rotate when power is applied to
the module and control signal > approx. 2 VDC
Fan does not rotate 100% at max. control signal
10 VDC

11.3 Start-up after rectification of fault

After correction of the fault, carry out the following steps for recommissioning:
1. Make sure that all maintenance covers and access openings are sealed.
2. Switch off the unit.
3. Acknowledge the fault on the controller, if necessary.
Possible cause
Air in the heat exchanger.
Speed too high.
Air inlet/outlet opening is obstructed.
Filter dirty.
Rotating parts unbalanced
Fan dirty.
Heat exchanger dirty.
Possible cause
Mechanical blockage.
Control voltage poles switched.
Maximum limit set incorrectly.
Active temperature management effective (mo-
tor or electronics overheated).
Assembly, installation and operating instructions
Remedy
Vent heat exchanger.
Set a lower speed, if possible.
Free air ducts.
Replace filter.
Clean and/or replace impeller. Please make sure
that no balancing clips are removed during
cleaning.
Clean dirt from fan.
Clean dirt from Heat exchanger.
Remedy
Switch off, de-energise and remove the mechan-
ical blockage.
Connect the control voltage correctly.
Change potentiometer setting in the motor junc-
tion box.
Check that the airways are clear; remove any
foreign bodies, impeller is blocked or dirty; check
supply air temperature; check installation loca-
tion (air speed over heat sink).