Faults; Fault Table - Kampmann TIP Assembly, Installation And Operating Instructions

Table of Contents

Advertisement

TIP
Assembly, installation and operating instructions
11

Faults

The following chapter describes possible causes of faults and the work needed to rectify them. Should faults occur frequently,
shorten the maintenance intervals in line with the actual loading on the unit.
Contact the manufacturer with any faults that cannot be rectified using the following information.
Behaviour in the event of faults
The following applies:
1. Immediately switch off the unit with faults that pose an immediate danger to persons or property!
2. Determine the cause of the fault!
3. Switch off the unit and prevent it from being reconnected if rectifying the fault requires work in the hazard area. Immedi-
ately advise a supervisor on site about the fault.
4. Either rectify the fault yourself or have it repaired by authorised personnel, depending on the nature of the fault.
The Fault table [} 38] provides information on who is authorised to rectify and remedy faults.

11.1 Fault table

Fault
No function.
Fan is not running.
Water outlet
Unit is not heating sufficiently (LPHW)
38
Possible cause
No power supply.
Unit is switched off.
No power supply.
Electrical cable not connected or incorrectly con-
nected.
No request from controller, hence fans switch
off.
Fan blocked.
Impermissible operating pressure (e.g. excessive
back pressure)
Temperature monitor has tripped.
Motor winding interrupted.
Fault on the heat exchanger.
Hydraulic connection not properly done.
Fan is not switched on.
Air volume is too low.
Filter is dirty.
No heating or cooling medium.
Valves not operating.
Water volume too low.
Setpoint temperature on the controller set too
low.
Operating unit with integral sensor and/or ex-
ternal sensor is exposed to direct sunlight or po-
sitioned over a heat source.
Air cannot blow out or in freely.
Heat exchanger dirty.
Remedy
Check voltage, switch on repair switch.
Replace fuse.
Switch on the unit via the controller.
Check power supply and connect.
Check electrical connection and correct if neces-
sary.
Change controller settings, if required.
Clean dirt from fan.
Correct operating point. Allow unit to cool
down.
Allow the motor to cool down, find and rectify
the cause of the fault and release restart lock if
necessary.
Replace unit.
Replace the heat exchanger if you need to.
Check flow and return and tighten, if necessary.
Switch on fan at controller.
Set a higher speed.
Replace filter.
Switch on heating and/or cooling system, switch
on circulation pump, vent unit/system.
Replace faulty valves.
Check pump output, check hydraulics.
Adjust temperature setting on the controller.
Place operating unit with integral sensor and/or
external sensor in a suitable position.
Remove obstacles at the air outlet/air inlet.
Clean heat exchanger.

Advertisement

Table of Contents
loading

Table of Contents