Installation and wiring

6.1

Requirements governing the installation site

Only install and assemble the unit if the following conditions are met:
Make sure that the wall/ceiling is sufficiently load-bearing to take the weight of the unit (Technical data [} 12]).
Make sure that the unit is securely suspended/standing.
Ensure that the airflow can circulate freely.
Provide adequate space for appropriately sized flow and return water connections on site (Connection to the pipe
network [} 19]).
There is a power supply on site (Maximum electrical rating values [} 21]).
6.2

Minimum clearances

Unit heaters can be installed free-standing or suspended from the wall using the wall brackets supplied or suspended from
the ceiling using the ceiling brackets supplied. Installation using existing wall or ceiling brackets is also possible.
A minimum distance L in accordance with the table below must be respected between the suction zone of the unit and the
wall/ceiling! If you do not leave this minimum distance, the unit heater output will be reduced and the noise level will in-
crease.
Be sure to observe the minimum distances when using accessories or for maintenance purposes!
L min
Fig. 2: Minimum distances, TIP
Series
54
55
56
Tab. 5: Overview of types with minimum distances
* when using wall brackets, type 3_044
14
Type
54_57
55_57
56_57
Minimum distance L min
160 mm
180 mm
230 mm
Standard clearance L*
285 mm
285 mm
335 mm