7.1

Maximum electrical rating values

Electromechanical version (type ... 57)
Type
54**57
55**57
56**57
Tab. 8: Electrical data, TIP
Type
Speed controller, type 30510
Room thermostat, type 30155
Clock thermostat 230 V, type 30256
Electronic speed controller, type 30515
Tab. 9: Maximum connectible unit heaters with EC fan per speed control unit
7.2

Electromechanical control

EMC-compliant installation of control cables
To avoid interference, ensure there is sufficient clearance between the mains power and control cables. When using a shiel-
ded cable, make sure that the shield is connected just on one side, i.e. only to the signal source with the protective earth (as
short and low inductance as possible)!

7.2.1 Connection (**00)

Fig. 10: TIP with motor junction box
22
Nominal
Mains fre-
voltage [V]
quency [Hz]
230
50/60
230
50/60
230
50/60
Active
Nominal
power [kW]
current [A]
0.17
1.2
0.42
1.9
0.42
1.9
Number
10
2
2
10
Power supply and control
All sizes require a power supply of 230 V / 50/60 Hz and can
be activated via a control input of 0-10 VDC (Ri > 49 KOhm).
Leakage cur-
Maximum
rent [mA]
pre-fusing
[A]
0.6
B10
0.6
B10
0.6
B10
IP class
Protection
class
44
I
44
I
44
I