Trane RTXC XE Series Installation Operation & Maintenance page 13

Air-to-water screw heat pump
Table of Contents

Advertisement

Note: In case of the height of enclosure around the unit higher than 1.5m, contact Trane local
office.
Figure 3- 4 Installation Clearance - Multi-Unit
Figure 3 Acceptable Minimum Clearances
NOTICE - No obstructions to outdoor fan airflow exit, including ductwork.
If the unit location requires a variance to the clearance dimensions, or any walls or enclosure around
the unit, contact your Trane sales office representative.
Drainage
Locate the unit near a large capacity drain for water drain from evaporator during shutdown or repair, or the
condensate water generated by coil during defrost. A drain connection is located at the bottom of the
evaporator waterbox. Also, remove the vent plugs at the top of the waterbox to facilitate complete drainage.
All local and national codes apply.
WARNING - Hazardous Voltage!
No stagnant water on the installation site, and the water drainage pipes must be ensured to prevent
water from entering the electric control box.
Failure to do so may result in equipment damage, electricity leakage, personal injury, or death.
On installations where low ambient temperature application is intended and snow accumulations are
expected, additional elevation must be provided to ensure electrical safety.