Trane RTXC XE Series Installation Operation & Maintenance page 21

Air-to-water screw heat pump
Table of Contents

Advertisement

CAUTION - Equipment Damage!
After water system clean and leakage test, fully drain the water from evaporator and piping system.
Use pressurized air or nitrogen to blow out and ensure that no water stay in the evaporator and
piping in winter.
CAUTION - Equipment Damage!
All inlet and outlet shutoff valves shown in
by UC800 controlled pump to avoid freezing when the units in operation or standby condition.
[3
d
SHUTOFF VALVE
VIBRATION
ELIMINATOR
l=?
WATER STRAINER
Entering Water Piping
Water strainer
Vibration eliminators
Water pressure gauges with shutoff valves
Thermometers (if desired)
Shutoff (isolation) valves
Drain valve
Leaving Water Piping
Drain valve
Shutoff (isolation) valves
Vibration eliminators
Balancing valve
Thermometers (if desired)
Flow switch
Water pressure gauges with shutoff valves
Air vents (to bleed air from system)
Minimum Water Loop Volume
In order to obtain leaving water temperature stability for comfort cooling applications, a minimum water loop
volume of 9 liters per kW is recommanded on all unit sizes. If the total water system volume lower than
required, including water volume of evaporator, water piping and indoor unit, it may be necessary to add a
tank or increase pipe sizes to provide sufficient liquid volume. Any storage tank that is placed in the water
loop should have internal baffles to allow thorough mixing of the fluid.
Figure 8
Figure 8 Typical chilled water piping system diagram
WATER PUMF
-w
©
CHECK VALVE
©
BALANCE VALVE
should be always open to enable water circulated
PRESSURE GAGE
INDOOR UNIT [J
THERMOMETER
RELIEF VALVE
FLOW SWITCH
AIR VENT VALVE
21
EXPANSION TANK