Trane 4TYK6524D1000AL Installation, Operation And Maintenance Manual page 10

U-match dc inverter system r-410a up to16 seer outdoor unit - cooling only and heat pump 24,000 to 60,000 btu/h - 60hz

Advertisement

Unit Installation
IMPORTANT NOTE:
These instructions are intended to provide a method of installation of the unit to the concrete base
in order to establish a protective procedure in cases of strong winds. It is recommended to verify
local codes for the application of methods and protocols for secure setting of the unit.
Figure 4. Preferred Method for Unit Setting
Cautions to be Observed During Installation of Refrigerant Lines
1. Install lines with the least amount of curves possible. Avoid damaging line couplings or line
2. Install lines avoiding any obstructions to the coil, to the air handling components o to the filter.
3. Take special care in the application of insulation to refrigerant lines in order to minimize the
4. When applying insulation material to the suction line, refrigerant lines should be supported as
5. Use PVC piping as conduit in all underground installations. See Figure 6. Underground lines
6. In an effort to reduce vibrations and to retain some degree of flexibility, place a type of sealant
10
#7 X 3/8" drill screws
(Not to exceed 3/8" in length)
(Pilot hole required 3/16". Pilot hole should be 1/4" deeper than the space
occupied by the bracket).
curves. Use clean and hard drawn copper tubing at points where it will not be necessary to
apply multiple curves around obstructions. When it is necessary to use soft copper, it should
be carefully applied avoiding sharp curves that may provoke any type of restriction.
transmission of sound to the structure.
illustrated in Figure 5. DO NOT allow any friction contact between metal piping.
should be kept as short as possible in order to minimize the accumulation of liquid refrigerant
in the suction line during extended system shutdown periods.
material like permagum or similar around refrigerant lines that must be directed through walls.
See Detail B
Brackets:
height as required.
DETAIL B
MS-SVN052E-EN