POWERPATH PS-8-LP Installation Instructions Manual page 11

Nac extender power supplies
Table of Contents

Advertisement

L
GND
N
AC LOSS Form "C"
Relay Terminals
AC LOSS TRB
COM
D21
NO
NC
TB1
Table 1: Power Supply/Battery Charger PC Board Terminal Identification
Terminal Block
Identification
Identification
Numbers (Figure 4)
TB1 - 1,2,3
TB2 - 1,2,3
TB2 - 1,2,3
TB3 - 1,2
JP1 - 1,2
P84905-002 A
AC Input
AC Input
120VAC
240VAC
50 – 60 Hz
50 – 60 Hz
(PS-6, PS-8-LP)
(PS-6E, PS-8-LPE)
MICROPROCESSOR TROUBLE
BATTERY
POWER
D36
D35
D24
D38
POWER
J2
Figure 4: Power Supply/Battery Charger PC Board
Terminal
AC Trouble
Form "C" contacts rated 24VDC at 1 Amp used for external trouble alerts.
AC Input
Input power terminals for 120VAC, 50 to 60 Hz. Non-Power Limited (PS-6, PS-8-LP)
Input power terminals for 240VAC, 50 to 60 Hz. Non-Power Limited (PS-6E, PS-8E-
AC Input
LP)
Backup battery terminals: 24VDC, 7 to 33 Ahrs, Sealed Lead Acid Non-Power Limited.
Battery
All Models – Two 12VDC 7 Ahrs batteries fit inside the enclosure. Batteries larger
than 7 Ahrs require an external enclosure such as the Wheelock Product BATC.
Jumper Sets Delay for Remote AC LOSS Annunciation.
JP1
JP1 IN = 0 Min Delay
firealarmresources.com
BATTERY CHARGER TROUBLE
BATTERY TROUBLE
D34
AC LOSS DELAY
JP1 IN = 0 MIN
JP1 OUT = 170 MIN
JP1
Function/Description
JP1 OUT = 170 Min Delay
Battery Terminals
24VDC, 7 to 33 Ahrs
Sheet 11 of 37
TB3
BATTERY

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PS-8-LP and is the answer not in the manual?

Questions and answers

Table of Contents