ATTENTION: FSX Power-Up – After the application of 24 VDC input power or resetting the Detector,
wait a mimimum of (thirty) 30 seconds to allow the Detector's sensors to normalize to the
environment's spectral background conditions.
FSX Testing - As with any intelligent flame or fire Detector, please wait a minimum of
thirty (30) seconds between tests (i.e., butane lighter, FSC test lamp, or test fires) to
allow the Detector's sensors to fully normalize to the spectral background conditions.
Changing the Detector Settings – To activate changes to the settings using SW1,
SW2 and SW3, reset the Detector by cycling (OFF, then ON) 24 VDC input power.
1. Verify that the external 24 VDC input power is turned OFF before connecting the Detector.
2. Avoid wire splices whenever possible. If wire splices are required, solder and properly insulate them.
Good wiring practices simplify installation, improve reliability, and facilitate maintenance.
3. For applications requiring analog/digital communications, please refer to Section 3.2 of this Instruction
Manual.