McQuay MWM09J Manual page 16

Wall mounted split systems
Table of Contents

Advertisement

MWM-J_(ii)
Cooling Unit (single phase)
Indoor Unit
*** Outdoor coil sensor connection wire
Terminal Block
(8m long) attached in the indoor unit
COMP
N1
N
L
Heat Pump Unit (single phase)
Indoor Unit
Outdoor coil sensor connection wire
Terminal Block
(8m long) attached in the indoor unit
4WV
OF
COMP
N1
N
L
Outdoor Unit
Terminal Block
COMP
N
Power Supply Cable
There must be a double pole switch
with a minimum 3mm contact gap and
fuse/circuit breaker as recommended
in the fixed installation circuit.
Outdoor Unit
Terminal Block
4WV
OF
COMP
N
Power Supply Cable
There must be a double pole switch
with a minimum 3mm contact gap and
fuse/circuit breaker as recommended in
the fixed installation circuit.
Model
Voltage range**
2
Power supply cable size*
mm
Number of wire
2
Interconnection cable size* mm
Number of wire
Recommended fuse
A
Model
Voltage range**
Power supply cable size*
mm
2
Number of wire
2
Interconnection cable size* mm
Number of wire
Recommended fuse
A
Application Information
M(5)WM09/10/15J
M(5)WM20/25J
M(5)LC09/10/15C
M(5)LC20/25C
220V-240V/1Ph/50Hz +
1.5
2.5
3
3
1.5
2.5
3
3
15
20
M(5)WM09/10/15JR
M(5)WM20/25JR
M(5)LC09/10/15CR
M(5)LC20/25CR
220V-240V/1Ph/50Hz +
1.5
2.5
3
3
1.5
2.5
3
3
15
20
14