8

Maintenance

Maintenance and annual startup
Table 8A_Service and Maintenance Schedules
Service technician
(see the following pages for instructions)
General:
• Address reported problems
• Inspect interior; clean and vacuum if
necessary;
• Check for leaks (water, gas, flue,
condensate)
• Examine venting system
• Check system water pressure/system
piping/expansion tank
• Check control settings
• Check igniter
• Check wiring and connections
• Check flue gas passageways
• Flame inspection (stable, uniform)
• Inspect and clean the burner
• Check manifold gas pressure
• Perform
performance verification per Section 6 in
the Copper-fin
Manual.
If
combustion
indicate need:
• Clean heat exchanger with a stiff bristle
brush
• Remove
water. Dry before re-assembling.
• Clean the blower wheel with a brush and
vacuum. Do not let dirt from cleaning get
pulled into the blower.
60
start-up
checkout
Installation and Operation
2
or
performance
and
clean
burners
using
Installation & Operation Manual
Owner maintenance
Daily
Monthly
Periodically
and
Every
6 months
End
of season
months
• Check appliance area
• Check pressure/temperature
gauge
• Check vent piping
• Check air piping
• Check relief valve
• Replace combustion air filter
Note: More frequent replacement may
be necessary in dirty environments.
• Test low water cutoff (if used)
• Reset button (low water cutoff)
• Check appliance piping (gas and
water) for leaks
• Operate relief valve
• Shut appliance down