Electrical connections

Pool heater operating control module

The operating control for the appliance is the SMART
SYSTEM control module. It is located on the inside of the
control panel, behind the front access door. Access to adjust
the temperature set point and other user adjustable points
is made through the Operator Interface located on the front
access door.
The exact temperature set point is based on the system's
requirements. Set the control set point(s) to the desired
operating water temperature.
The maximum temperature set point that can be programmed
into the control module from the Operator Interface on a
pool heater is 105°F (40.5°C). The manual reset high limit
control for a pool heater is adjustable up to a fixed maximum
setting of 200°F (93°C).
TABLE - 5C
AMP DRAW DATA
Model Controls Blower
502
3.6
2.7
652
5.4
3.4
752
5.4
3.4
992
7.3
3.2
1262
7.3
3.2
1442
7.3
6.7
1802
7.3
6.7
2072
7.3
6.7
*With standard factory supplied pump.
ELECTRICAL SHOCK HAZARD – For your
⚠WARNING
safety, turn off electrical power supply before
making any electrical connections to avoid
possible electric shock hazard. Failure to do
so can cause severe personal injury or death.
Wiring must be N.E.C. Class 1.
NOTICE
If original wiring as supplied with the pool
heater must be replaced, use only type 105°C
wire or equivalent.
Pool heater must be electrically grounded as
required by National Electrical Code ANSI/
NFPA 70 – latest edition.
(continued)
Pump
Approximate Total
FLA*
Amps @ 120 VAC
5.8
12.1
5.8
14.6
5.8
14.6
7.4
17.9
7.4
17.9
7.4
21.4
8.8
22.8
8.8
22.8
Installation & Operation Manual
Label all wires prior to disconnection when
⚠ CAUTION
servicing controls. Wiring errors can cause
improper and dangerous operation.
Verify proper operation after servicing.
Installation must comply with:
1. National Electrical Code and any other national, state,
provincial, local codes, or regulations.
2. In Canada, CSA C22.1 Canadian Electrical Code Part 1, and
any local codes.
Line voltage connections
1. Connect 120 VAC power wiring to the line voltage
terminal strip in the junction box, as shown in FIG. 5-2.
2. Provide and install a fused disconnect or service switch
(15 AMP recommended) as required by the code (see
FIG. 5-2).
3. To activate the unit, wire as shown in FIG. 5-2. If the
motor is larger than 1 HP, you must install a contactor.
4. When connecting power to units which are to be
cascaded, each unit must be connected to the same ground
connection.
UNIT
UNIT PUMP
SUPPLY
SUPPLY
L N G
L
N G
D
D
I
I
S
S
C
C
O
O
N
N
N
N
E
E
C
C
T
T
UNIT
PUMP
GROUND
SPLICE
L
N
UNIT
120V
PUMP
SUPPLY
1 HP MAX
Figure 5-2_Line Voltage Field Wiring Connections
CHASSIS
GROUND
45