Rheem RTGH-C95XLP Use And Care Manual page 34

High efficiency commercial condensing tankless
Table of Contents

Advertisement

INSTALLATION INSTRUCTIONS
Venting for Direct-Vent Water Heater
DANGER:
Failure to properly vent the water heater to the outdoors
as outlined in this Venting section will result in death or
serious personal injury. To avoid the risk of fire, explosion,
or asphyxiation from carbon monoxide, NEVER operate the
water heater unless it is properly vented and has adequate
air supply for proper operation as outlined in this Venting
section. This water heater must have air supply connected
and terminated to the outdoors.
WARNING:
Refer to page 29 for required clearances to combustible
materials. Improper clearances can cause explosion or fire
resulting in death, personal injury, and/or product damage.
CAUTIONS:
• Check to make sure flue gases do not recirculate into the
air intake terminal when using direct venting. If the water
heater is having service issues, flue recirculation may be a
contributing factor.
• Even when the minimum vent terminal separation
distances are followed, recirculation may still occur
depending upon the location outside the building, the
distance from other buildings, proximity to corners,
weather conditions, wind patterns, and snow depth.
• Periodically check to make sure that flue recirculation
is not occurring. Signs of flue gas recirculation include
frosted or frozen intake terminals and condensate in the
intake terminal and venting system.
• Correction to flue recirculation may involve angling the
intake away from the exhaust terminal and increasing the
distance between them. Check to be sure the intake and
exhaust terminals are not obstructed, especially during
periods of below-freezing weather.
Venting Requirements
The installation of venting must comply with national
codes, local codes, and the vent manufacturer's
instructions.
The vent exhaust and air intake must terminate outside
as described in these instructions. DO NOT vent this
water heater through a chimney. It must be vented
separately from all other appliances.
NOTICE:
The unit can be vented using only the following approved
vent pipe material.
Use only 2, 3 or 4 inch diameter pipe. Refer to local
codes for restrictions on the use of InnoFlue® PP , PVC,
CPVC, or ABS pipe and fittings. All exhaust venting
materials for product installed in Canada must meet
ULC-S636.
34
The use of cellular core PVC (ASTM F891), cellular
core CPVC, or Radel® (polyphenolsulfone) in non-
metallic venting systems is prohibited and that
covering non-metallic vent pipe and fittings with
thermal insulation is prohibited.
This water heater requires a special venting system.
Refer to venting supplier's instruction for complete parts
list and method of installation. The manufacturers and
product lines listed on the following tables have been
tested and authorized to safely operate with Rheem
tankless water heater.
Approved Vent Materials, Fittings and Terminations:
PVC
Acceptable Materials
Schedule 40,
for Exhaust
ASTM D-1785
Acceptable Materials
Schedule 40,
for Air Intake
ASTM D-1785,
and DWV,
ASTM-D2665
Fittings
Schedule 40,
ASTM D-2665
Terminations
RXGY-G01
(Manufactured
RXGY-G02
by Polytech)
PTX-129
RXGY-E03A
RXGY-G01C
ABS is not permitted for exhaust vent in Canada
Approved Polypropylene Vent Manufacturer/Trade Name:
Manufacturer
Centrotherm
Trade Name
InnoFlue®
Single Wall Pipe
ISVL**** or ISVL****UV
Elbow
ISELL**** or ISELL****UV
Adapter
ISAGL0303
Non-Return Valve (NRV)
ISNRV****
Siphon
IASJBVS
Termination
ISLPT**** or ISTT****
*Refers to variations in nominal size.
DO NOT USE Schedule 20, Cell Core, Drain Pipe,
Galvanized, Aluminum, B-Vent, or any flexible vent.
CPVC
ABS
Schedule 40,
Schedule 40,
ASTM F-441
ASTM D-2661
Schedule 40,
Schedule 40,
ASTM F-441,
ASTM D-2661
and CPVC 4120,
ASTM-D2846
Schedule 40,
Schedule 40,
ASTM F-438
ASTM D-2661

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rtgh-c95dvln

Table of Contents