Troubleshooting - Kohler K-2975 Installation Manual

Hide thumbs Also See for K-2975:
Table of Contents

Advertisement

Available languages

Available languages

Adjust the Shower Temperature (cont.)
NOTE: While rotating the detent collar, small in-and-out
adjustments will be required to ensure the collar does not engage
the cartridge teeth. Use the detent collar to rotate the spline adapter.
While rotating the collar and spline adapter, monitor the water
outlet temperature.
When the temperature reaches 104-105°F (40-40.5°C), push the
detent collar in until it engages the teeth of the cartridge.
With the clip tab positioned toward the valve, reinstall the clip to
the head nut.
Using the volume control valve (not shown), turn off the water.

Troubleshooting

Symptoms
Only hot or cold water from
1.
the water outlet.
Fluctuating or reduced flow
2.
rate.
3.
No flow from shower control
water outlet.
Kohler Co.
Probable Cause/Recommended
Action
A. Inlet supplies are reversed. See
"Reverse the Inlet Supplies"
section.
B. Check filter screens for
blockage. Clear if necessary.
A. External condition variation
such as reduced pressure.
B. Check filter screens for
blockage. Clear if necessary.
C. Make sure that the minimum
flow rate is sufficient for supply
conditions.
D. Make sure that dynamic inlet
pressures are nominally balanced
and sufficient.
E. Make sure that inlet
temperature differentials are
sufficient.
F. Service stops are not fully
opened. Rotate both service stops
clockwise until fully open.
G. Check thermostatic
performance; replace the
thermostatic cartridge, if necessary.
A. Filter screens are blocked. Clear
filter screens.
21
1145568-2-A

Advertisement

Table of Contents
loading

This manual is also suitable for:

K-2972K-2973K-2976

Table of Contents